background image

4 Installation

Installation manual

8

08S18+23DA + 08S18+23DJ

Daikin Altherma 3 R F

4P584429-1 – 2019.06

3.2

Preparing water piping

NOTICE

In  case  of  plastic  pipes,  make  sure  they  are  fully  oxygen
diffusion  tight  according  to  DIN  4726.  The  diffusion  of
oxygen into the piping can lead to excessive corrosion.

Valve  towards  expansion  vessel.

  The  valve  towards  the

expansion vessel (if equipped) MUST be open.

3.2.1

To check the water volume and flow rate

Minimum water volume

There are no requirements for the minimum water volume.

Minimum flow rate

Check that the minimum flow rate in the installation is guaranteed in
all  conditions  on  each  zone  separately.  This  minimum  flow  rate  is
required  during  defrost/backup  heater  operation.  For  this  purpose,
use the overpressure bypass valve delivered with the unit.

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).

See the installer reference guide for more information.

Minimum required flow rate

12 l/min

See  the  recommended  procedure  as  described  in 

"6.2  Checklist

during commissioning" on page 24

.

3.3

Preparing electrical wiring

3.3.1

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Outdoor unit and indoor unit power supply

1

Power supply for
outdoor unit

2+GND

(a)

2

Power supply and
interconnection cable to
indoor unit

3

(f)

3

Power supply for
backup heater

See table below. —

4

Preferential kWh rate
power supply (voltage
free contact)

2

(d)

5

Normal kWh rate power
supply

2

6.3 A

Optional equipment

6

User interface used as
room thermostat

2

(e)

7

Room thermostat

3 or 4

100 mA

(b)

8

Outdoor ambient
temperature sensor

2

(b)

9

Indoor ambient
temperature sensor

2

(b)

10

Heat pump convector

2

100 mA

(b)

Field supplied components

Item

Description

Wires

Maximum

running

current

11

Shut-off valve

2

100 mA

(b)

12

Electricity meter

2 (per meter)

(b)

13

Domestic hot water
pump

2

(b)

14

Alarm output

2

(b)

15

Changeover to external
heat source control

2

(b)

16

Space heating
operation control

2

(b)

17

Power consumption
digital inputs

2 (per input
signal)

(b)

18

Safety thermostat for
the main zone

2

(b)

19

Safety thermostat for
the additional zone

2

(d)

(a)

Refer to name plate on outdoor unit.

(b)

Minimum cable section 0.75 mm².

(c)

Cable section 2.5 mm².

(d)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

(e)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m.

(f)

Cable section 1.5 mm².

NOTICE

More  technical  specifications  of  the  different  connections
are indicated on the inside of the indoor unit.

NOTICE

A  safety  thermostat  (normal  closed  contact)  MUST  be
installed  for  the  main  zone.  See 

"4.5.12  To  connect  the

safety thermostat (normally closed contact)" on page 16

.

Backup heater

type

Power supply

Required number of

conductors

*6V

1N~ 230 V (6V)

2+GND

3~ 230 V (6T1)

3+GND

*9W

3N~ 400 V

4+GND

4

Installation

4.1

Opening the units

4.1.1

To open the indoor unit

1

Remove the top panel.

Summary of Contents for Altherma EHVZ08S23DA6V

Page 1: ...Altherma 3 R F English Installation manual Daikin Altherma 3 R F EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ08S18DA9W G EHVZ08S23DA9W G EHVZ04S18DJ6V G EHVZ08S18DJ6V G EHVZ08S23DJ6V G EHVZ08...

Page 2: ...du s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im upu...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...nd date 18 5 2 3 Configuration wizard System 18 5 2 4 Configuration wizard Backup heater 19 5 2 5 Configuration wizard Main zone 19 5 2 6 Configuration wizard Additional zone 20 5 2 7 Detailed screen...

Page 5: ...e refrigerant pipes or clean thoroughly 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Spac...

Page 6: ...ion Installation manual 6 EHVZ04 08S18 23DA EHVZ04 08S18 23DJ Daikin Altherma 3 R F 4P584429 1 2019 06 NOTICE Pipework shall be protected from physical damage Installation of pipework shall be kept to...

Page 7: ...Use table 3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings...

Page 8: ...y 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 f 3 Power supply for backup heater See table below 4 Preferential kWh rate power supply voltage free...

Page 9: ...ower the switch box on the indoor unit on page 9 4 2 2 To connect the drain hose to the drain on page 10 When you need access to the high voltage switch box 4 1 2 To open the switch box cover of the i...

Page 10: ...he drain pan The drain pan is connected to a drain hose inside the unit You must connect the drain hose to an appropriate drain according to the applicable legislation You can route the drain hose thr...

Page 11: ...ter in c Domestic hot water out d Domestic cold water in cold water supply e Space heating main zone water out f Space heating main zone water in NOTICE It is recommended to install shut off valves to...

Page 12: ...unit 1 To open the indoor unit see 4 1 1 To open the indoor unit on page 8 and 4 1 2 To open the switch box cover of the indoor unit on page 9 2 The wiring enters the unit from the top b c a d a b c F...

Page 13: ...pply WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed...

Page 14: ...actor in the lower switch box K5M Safety contactor in the lower switch box Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the back...

Page 15: ...ector backup heater Do NOT change 2 Fix the cable with cable ties to the cable tie mountings 4 5 9 To connect the space heating ON OFF output 1 Connect the space heating ON OFF output cable to the app...

Page 16: ...rmostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety thermostat and the 3 way valve INFOR...

Page 17: ...nstaller settings on page 23 5 1 1 To access the most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Ente...

Page 18: ...ng Menu structure setting 9 2 1 replaces the following 3 overview settings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of do...

Page 19: ...y 1 2 a 2 Relay 1 Relay 2 a 3 Relay 1 Relay 2 Emergency Relay 1 2 a a Not available for 3V models INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you chang...

Page 20: ...aving water temperatures either preset or custom In Weather dependent LWT setpoint mode the scheduled actions consist of desired shift actions either preset or custom Code Description 2 1 N A 0 No 1 Y...

Page 21: ...reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has...

Page 22: ...rmostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OF...

Page 23: ...step 2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum run...

Page 24: ...e of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pi...

Page 25: ...e 17 2 Go to A 1 Commissioning Operation test run 3 Select a test from the list Example Heating 4 Select OK to confirm Result The test run starts It stops automatically when done 30 min To stop the te...

Page 26: ...setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to sta...

Page 27: ...mixed zone c1 Domestic hot water cold water IN c2 Domestic hot water hot water OUT d1 Gas refrigerant IN heating mode condenser d2 Liquid refrigerant OUT heating mode condenser e Plate heat exchanger...

Page 28: ...ostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in swit...

Page 29: ...e 5 Ext thermistor 5 External thermistor SWB Switch box 6 Field supplied options 6 Field supplied options English Translation 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse detection vo...

Page 30: ...signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 2 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H onl...

Page 31: ...0 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between...

Page 32: ...4P584429 1 2019 06 Copyright 2017 Daikin 4P584429 1 0000000U...

Reviews: