4 Installation

Installation manual

11

08S18+23DA + 08S18+23DJ
Daikin Altherma 3 R F
4P584429-1 – 2019.06

b

Refrigerant gas connection

2

Connect  the  gas  stop  valve  from  the  outdoor  unit  to  the
refrigerant gas connection of the indoor unit.

INFORMATION

When  the  indoor  unit  is  installed  in  a  place  with  limited
space,  an  optional  pipe  bend  (EKHVTC)  kit  can  be
installed  to  facilitate  the  connection  to  the  refrigerant  gas
and  liquid  connections  of  the  indoor  unit.  For  installation
instructions, see the instruction sheet of the pipe bend kit.

4.4

Connecting the water piping

4.4.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.

To  facilitate  service  and  maintenance,  4  shut-off  valves  and  1
overpressure  bypass  valve  are  provided.  Mount  the  shut-off  valves
on  the  space  heating  water  inlets  and  space  heating  water  outlets.
To ensure the minimum flow rate (and prevent overpressure), install
the 

overpressure  bypass  valve

  on  the  space  heating  water  outlet

for the 

additional zone

.

NOTICE

This unit is designed for operation on 2 temperature zones:

▪ underfloor  heating  in  the 

main  zone

,  this  is  the  zone

with the 

lowest water temperature

,

▪ radiators  in  the 

additional  zone

,  this  is  the  zone  with

the 

highest water temperature

.

1

Install the shut-off valves on the space heating water pipes.

2

Screw the indoor unit nuts on the shut-off valve.

3

Connect  the  domestic  hot  water  in  and  out  pipes  to  the  indoor
unit.

c d a b

f

e

a

Space heating additional zone water out

b

Space heating additional zone water in

c

Domestic hot water out

d

Domestic cold water in (cold water supply)

e

Space heating main zone water out

f

Space heating main zone water in

NOTICE

It  is  recommended  to  install  shut-off  valves  to  domestic
cold  water  in  and  domestic  hot  water  out  connections.
These shut-off valves are field supplied.

NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

Mind  the  minimum  flow  rate  when  adjusting  the
overpressure  bypass  valve  setting.  See 

"3.2.1  To  check

the  water  volume  and  flow  rate"  on  page  8

  and 

"6.2.1  To

check the minimum flow rate" on page 24

.

NOTICE

If you install this unit as a single-zone application, then:

Setup.

  Install  a  bypass  between  the  space  heating  water

inlet  and  outlet  of  the  additional  zone  (=direct  zone).  Do
NOT interrupt the water flow by closing the shut-off valves.

a

a

 Bypass

Configuration.

  Set  field  setting  [7-02]=0  (

Number  of

zones

 = 

Single zone

).

NOTICE

Install air purge valves at all local high points.

NOTICE

A  pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=  1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

4.4.2

To connect the recirculation piping

Prerequisite: 

Only required if you need recirculation in your system.

1

Remove  the  top  panel  from  the  unit,  see 

"4.1.1  To  open  the

indoor unit" on page 8

.

2

Cut out the rubber grommet on top of the unit, and remove the
stop. The recirculation connector is placed below the hole.

3

Route the recirculation piping through the grommet and connect
it to the recirculation connector.

4

Reattach the top panel.

4.4.3

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

Summary of Contents for Altherma EHVZ08S23DA6V

Page 1: ...Altherma 3 R F English Installation manual Daikin Altherma 3 R F EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ08S18DA9W G EHVZ08S23DA9W G EHVZ04S18DJ6V G EHVZ08S18DJ6V G EHVZ08S23DJ6V G EHVZ08...

Page 2: ...du s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im upu...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...nd date 18 5 2 3 Configuration wizard System 18 5 2 4 Configuration wizard Backup heater 19 5 2 5 Configuration wizard Main zone 19 5 2 6 Configuration wizard Additional zone 20 5 2 7 Detailed screen...

Page 5: ...e refrigerant pipes or clean thoroughly 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Spac...

Page 6: ...ion Installation manual 6 EHVZ04 08S18 23DA EHVZ04 08S18 23DJ Daikin Altherma 3 R F 4P584429 1 2019 06 NOTICE Pipework shall be protected from physical damage Installation of pipework shall be kept to...

Page 7: ...Use table 3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings...

Page 8: ...y 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 f 3 Power supply for backup heater See table below 4 Preferential kWh rate power supply voltage free...

Page 9: ...ower the switch box on the indoor unit on page 9 4 2 2 To connect the drain hose to the drain on page 10 When you need access to the high voltage switch box 4 1 2 To open the switch box cover of the i...

Page 10: ...he drain pan The drain pan is connected to a drain hose inside the unit You must connect the drain hose to an appropriate drain according to the applicable legislation You can route the drain hose thr...

Page 11: ...ter in c Domestic hot water out d Domestic cold water in cold water supply e Space heating main zone water out f Space heating main zone water in NOTICE It is recommended to install shut off valves to...

Page 12: ...unit 1 To open the indoor unit see 4 1 1 To open the indoor unit on page 8 and 4 1 2 To open the switch box cover of the indoor unit on page 9 2 The wiring enters the unit from the top b c a d a b c F...

Page 13: ...pply WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed...

Page 14: ...actor in the lower switch box K5M Safety contactor in the lower switch box Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the back...

Page 15: ...ector backup heater Do NOT change 2 Fix the cable with cable ties to the cable tie mountings 4 5 9 To connect the space heating ON OFF output 1 Connect the space heating ON OFF output cable to the app...

Page 16: ...rmostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety thermostat and the 3 way valve INFOR...

Page 17: ...nstaller settings on page 23 5 1 1 To access the most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Ente...

Page 18: ...ng Menu structure setting 9 2 1 replaces the following 3 overview settings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of do...

Page 19: ...y 1 2 a 2 Relay 1 Relay 2 a 3 Relay 1 Relay 2 Emergency Relay 1 2 a a Not available for 3V models INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you chang...

Page 20: ...aving water temperatures either preset or custom In Weather dependent LWT setpoint mode the scheduled actions consist of desired shift actions either preset or custom Code Description 2 1 N A 0 No 1 Y...

Page 21: ...reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has...

Page 22: ...rmostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OF...

Page 23: ...step 2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum run...

Page 24: ...e of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pi...

Page 25: ...e 17 2 Go to A 1 Commissioning Operation test run 3 Select a test from the list Example Heating 4 Select OK to confirm Result The test run starts It stops automatically when done 30 min To stop the te...

Page 26: ...setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to sta...

Page 27: ...mixed zone c1 Domestic hot water cold water IN c2 Domestic hot water hot water OUT d1 Gas refrigerant IN heating mode condenser d2 Liquid refrigerant OUT heating mode condenser e Plate heat exchanger...

Page 28: ...ostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in swit...

Page 29: ...e 5 Ext thermistor 5 External thermistor SWB Switch box 6 Field supplied options 6 Field supplied options English Translation 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse detection vo...

Page 30: ...signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 2 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H onl...

Page 31: ...0 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between...