![Daikin Altherma 3 R F EHVZ04S18E 6V Series Installer'S Reference Manual Download Page 61](http://html.mh-extra.com/html/daikin/altherma-3-r-f-ehvz04s18e-6v-series/altherma-3-r-f-ehvz04s18e-6v-series_installers-reference-manual_501222061.webp)
7
|
Unit installation
Installer reference guide
61
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
3
Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4
Attach the ends of the cables.
5
Tighten the cables.
7.4 Mounting the indoor unit
7.4.1 About mounting the indoor unit
When
You have to mount the outdoor and indoor unit before you can connect the
refrigerant and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1
Installing the indoor unit.
7.4.2 Precautions when mounting the indoor unit
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"1 General safety precautions"
▪
"7.1 Preparing the installation site"
7.4.3 To install the indoor unit
1
Lift the indoor unit from the pallet and place it on the floor. Also see
2
Connect the drain hose to the drain. See
"7.4.4 To connect the drain hose to
62].
3
Slide the indoor unit into position.
4
Adjust the height of the leveling feet to compensate for floor irregularities.
The maximum allowed deviation is 1°.