10
|
Configuration
Installer reference guide
156
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
#
Code
Description
[4.5]
[F-0D]
▪
2
Request
: Pump operation based on request.
Example:
Using a room thermostat and
thermostat creates thermo ON/OFF condition.
Remark:
NOT available in leaving water
temperature control.
a
d
e
b
b
c
b
c
c
a
Space heating control
b
Off
c
On
d
Heating demand (by external room thermostat
or room thermostat)
e
Pump operation
Unit type
In this part of the menu it can be read out which type of unit is used:
#
Code
Description
[4.6]
[E‑02]
Unit type
:
▪
0
Reversible
(only with EKHVCONV2
installed)
▪
1
Heating only
Pump limitation
The pump speed limitation for the main zone [9‑0E] and additional zone [9‑0D]
defines the maximum pump speed. In normal conditions, the default setting should
NOT be modified. The pump speed limitation will be overruled when the flow rate
is in the range of the minimum flow (error 7H).
#
Code
Description
[4.7]
[9-0D]
Pump limitation
Additional zone
:
▪
0:
No limitation
▪
1~4: General limitation. There is limitation in all
conditions. The required delta T control and
comfort are NOT guaranteed.
▪
5~8: Limitation when no actuators. When there
is no heating output, the pump speed limitation
is applicable. When there is heating output, the
pump speed is only determined by delta T in
relation to the required capacity. With this
limitation range, delta T is possible and the
comfort is guaranteed.