![Daikin Altherma 3 R F EHVZ04S18E 6V Series Installer'S Reference Manual Download Page 209](http://html.mh-extra.com/html/daikin/altherma-3-r-f-ehvz04s18e-6v-series/altherma-3-r-f-ehvz04s18e-6v-series_installers-reference-manual_501222209.webp)
13
|
Maintenance and service
Installer reference guide
209
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
a
b
a
a
Clip
b
Magnetic filter/dirt separator
8
Remove the water filter.
9
Remove the drain hose from the water filter.
CAUTION
Although the water circuit is drained, some water may be spilled when removing the
magnetic filter/dirt separator from the filter housing. ALWAYS clean up spilled water.
13.5.2 To clean the water filter in case of trouble
1
Remove the water filter from the unit. See
208].
CAUTION
To protect the piping connected to the magnetic filter/dirt separator from damage it
is recommended to perform this procedure with the magnetic filter/dirt separator
removed from the unit.
2
Unscrew the bottom of the water filter housing. Use an appropriate tool if
needed.
CAUTION
Opening the magnetic filter/dirt separator is ONLY required in case of severe issues.
Preferably this action is never to be done during the complete lifetime of the
magnetic filter/dirt separator.
a
b
a
Bottom part to be unscrewed
b
Water filter housing
3
Remove the strainer and the rolled‑up filter from the water filter housing and
clean with water.
4
Install the cleaned rolled‑up filter and strainer in the water filter housing.