![background image](http://html.mh-extra.com/html/daikin/altherma-3-r-ech2o/altherma-3-r-ech2o_installers-reference-manual_501188307.webp)
8/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
9.I
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
5°C
[2-0C]=2:
18°C
9.I
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
9.I
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.I
[0-07]
R/W
10~25°C, step: 1°C
20°C
9.I
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
9.I
[0-0C]
R/W
Min(45~[6-0E])
~
[6-0E]°C, step: 1°C
55°C
9.I
[0-0D]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.I
[1-02]
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
9.I
[1-03]
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
[2-0C]=0:
25°C
[2-0C]=1:
25°C
[2-0C]=2:
25°C
9.I
[1-04]
R/W
0: Disabled
1: Enabled
9.I
[1-05]
R/W
0: Disabled
1: Enabled
9.I
[1-06]
R/W
10~25°C, step: 1°C
20°C
9.I
[1-07]
R/W
25~43°C, step: 1°C
35°C
9.I
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
9.I
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
5°C
[2-0C]=2:
18°C
9.I
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9.I
[1-0B]
[2-0C]
≠
2:
R/W
[2-0C]=2:
R/O
3~10°C, step: 1°C
[2-0C]
≠
2 (Radiator):
5°C
[2-0C]=2 (Radiator):
10°C
9.I
[1-0C]
[2-0D]
≠
2:
R/W
[2-0D]=2:
R/O
[2-0D]
≠
2 (Radiator):
3~10°C, step: 1°C
5°C
[2-0D]=2 (Radiator):
8°C
9.I
[1-0D]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0E]
R/W
3~10°C, step: 1°C
5°C
9.I
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
9.I
[2-01]
R/W
0: No
1: Yes
9.I
[2-02]
R/W
0~23 hour, step: 1 hour
1
9.I
[2-03]
R/W
60°C
60°C
What is the desired delta T in cooling for the main zone?
What is the desired delta T in cooling for the additional zone?
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the disinfection target temperature?
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
What is the desired delta T in heating for the main zone?
What is the desired delta T in heating for the additional zone?
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Weather dependent cooling of the additional leaving water temperature zone
Low ambient temp. for LWT main zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
4P670988-1 - 2021.09
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) EKECBUA3V_(*7) EKECBUA6V_(*8) EKECBUA9W_(*9) BUH less_
(*10) 11P_(*11) 16P
Summary of Contents for Altherma 3 R ECH2O
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ...4P663482 1A 2021 11 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...