Disposal
Installer reference guide
278
ERLA11~W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1A – 2021.11
#
Action
7-segments display
(a)
1
Start from the default situation.
2
Select mode 2.
Press and hold
BS1
for 5 seconds.
3
Select setting 9.
Press
BS2
9 times.
4
Select value 2.
a
Display the current value.
Press
BS3
once.
b
Change the value to 2.
Press
BS2
once.
c
Enter the value in the system.
Press
BS3
once.
d
Confirm.
Press
BS3
once.
5
Return to the default situation.
Press
BS1
once.
(a)
= OFF,
= ON, and
= flashing.
Result:
The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
#
Procedure
7-segments display