Electrical installation
Installer reference guide
133
ERLA11~W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1A – 2021.11
—
A
B
X1M
1 2 3 4 5 6
A
B
2x
b
a
2x
a
1 2 3
b
L
N
F2B
1
3
2
4
I
I
Q DI
2
6
5
230 V AC, 6.3 A
1N~, 50 Hz,
a
Interconnection cable
b
Power supply indoor unit
In case of preferential kWh rate power supply
Interconnection cable
Wires: (3+GND)×1.5 mm²
Power supply indoor
unit
Wires: 1N+GND
Maximum running current: 6.3 A
Preferential kWh rate
power supply contact
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply contact:
16 V DC detection (voltage supplied by PCB). The
voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
[9.8]
Benefit kWh power supply