11
|
Configuration
Installer reference guide
184
ERLA11~W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1A – 2021.11
#
Code
Description
[2.6]
[1-06]
[1-07]
[1-08]
[1-09]
Set weather-dependent cooling in [2.6]
Cooling
WD curve
:
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
T
t
Target leaving water temperature (main zone)
T
a
Outdoor temperature
Set weather-dependent heating in [9.l]
Overview field settings
:
▪
[1-06]: Low outdoor ambient temperature.
10°C~25°C
▪
[1-07]: High outdoor ambient temperature.
25°C~43°C
▪
[1-08]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
ambient
temperature.
[9‑03]°C~[9‑02]°C
Note:
This value should be higher than [1‑09]
as for low outdoor temperatures less cold
water is required.
▪
[1-09]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
ambient
temperature.
[9‑03]°C~[9-02]°C
Note:
This value should be lower than [1‑08] as
for high outdoor temperatures colder water is
required.
Emitter type
Heating up or cooling down the main zone can take longer. This depends on:
▪
The water volume of the system
▪
The heater emitter type of the main zone
The setting
Emitter type
can compensate for a slow or a quick heating/cooling
system during the heat up/cool down cycle. In room thermostat control,
Emitter
type
influences the maximum modulation of the desired leaving water
temperature, and the possibility for usage of the automatic cooling/heating
changeover based on the indoor ambient temperature.
It is important to set
Emitter type
correctly and in accordance with your system
layout. The target delta T for the main zone depends on it.