Unit installation
Installer reference guide
73
ERLA11~W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1A – 2021.11
H
release
Actual release height:
1a
2a
: Without chimney. From floor to top of the unit.
▪
For 300 l units => H
release
=1.89 m
▪
For 500 l units => H
release
=1.90 m
1b
2b
: With chimney. From floor to top of the chimney.
▪
For 300 l units => H
release
=1.89 m + Chimney height
▪
For 500 l units => H
release
=1.90 m + Chimney height
3a
Installation with chimney connected to the outside. The release height
is not relevant. There are no requirements to the minimum floor area.
N/A
Not applicable
Minimum floor area / Release height:
▪
The minimum floor area requirements depend on the release height of the
refrigerant in case of a leakage. The higher the release height, the lower the
minimum floor area requirements.
▪
The default point of release (without chimney) is at the top of the unit. To
decrease the minimum floor area requirements, you can increase the release
height by installing a chimney. If the chimney leads outside of the building, there
are no requirements anymore to the minimum floor area.
▪
You can also take advantage of the floor area of the adjacent room (= room B) by
providing ventilation openings between the two rooms.
▪
For installations in technical rooms (i.e. room that is NEVER occupied by
persons), additionally to patterns 1, 2 and 3, you can also use
PATTERN
4
. For
this pattern there are no requirements to the minimum floor area if you provide
2 openings (one at the bottom, one at the top) between the room and the
outside to ensure natural ventilation. The room must be protected from frost.
When connecting a chimney
▪
Install the chimney socket (delivered as accessory) to the plate heat exchanger
box.
1×
1×
1×
1×
a
b
c
d
d
b
a
c
a
Chimney socket
b
Securing clip