8
|
Piping installation
Installer reference guide
98
EPRA08~W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1 – 2021.07
NOTICE
▪
The required concentration might differ depending on the type of glycol. ALWAYS
compare the requirements from the table above with the specifications provided
by the glycol manufacturer. If necessary, meet the requirements set by the glycol
manufacturer.
▪
The added concentration of glycol should NEVER exceed 35%.
▪
If the liquid in the system is frozen, the pump will NOT be able to start. Mind that
if you only prevent the system from bursting, the liquid inside might still freeze.
▪
When water is at standstill inside the system, the system is very likely to freeze
and get damaged.
Glycol setting
NOTICE
If glycol is present in the system, setting [E-0D] must be set to 1. If the glycol setting
is NOT set correctly, the liquid inside the piping can freeze.
Freeze protection by freeze protection valves
About freeze protection valves
It is the responsibility of the installer to protect the field piping against freezing.
When no glycol is added to the water, you can use freeze protection valves at all
lowest points of the field piping to drain the water from the system before it can
freeze.
To install freeze protection valves
To protect the field piping against freezing, install the following parts:
c
b
b
c
a
a
Automatic air intake
b
Freeze protection valve (optional – field supply)
c
Normally closed valves (recommended – field supply)
Part
Description
a
An automatic air intake (for air supply) should be installed at the
highest point. For example, an automatic air purge.
b
Protection for the field piping. The freeze protection valves must
be installed:
▪
vertically to allow water to flow out properly and free from
obstructions.
▪
at all lowest points of the field piping.
▪
in the coldest part and away from heat sources.
Note:
Leave at least 15 cm clearance from the ground to prevent
ice from blocking the water exit.