Electrical installation
Installer reference guide
118
EPRA08~W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1 – 2021.07
2
1
3
1
2
2
1
4
4,8 mm
It is important that the fixing plate of terminals is NOT in service position, while
cables are connected to one of the terminals. Otherwise the cables could be too
short.
X12M
9.3.2 To connect the main power supply
1
"7.2.5 To open the indoor unit"
72]):
1
User interface panel
1
3
4
2
2
Switch box
3
Switch box cover
4
Top cover
2
Connect the main power supply.
In case of normal kWh rate power supply
Interconnection cable
Wires: (3+GND)×1.5 mm²
Power supply indoor
unit
Wires: 1N+GND
Maximum running current: 6.3 A