5 Electrical installation
Installation manual
20
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569811-1 – 2019.02
Set overview field setting [C-0B]=1.
▪ If [C-0B]=0 (brine low pressure switch not installed), the unit
does not check the input.
▪ If [C-0B]=1 (brine low pressure switch installed), the unit
checks the input. If the input is "open", error EJ-01 occurs.
1
Open the following (see
"3.2.1 To open the indoor unit" on
):
1
Top panel
1
3
2
2
User interface panel
3
Installer switch box cover
2
Connect the brine low pressure switch cable as shown in the
illustration below.
2×
1×
A16P/X13A/1+4
1×
S1PL
P<
b
a
c
a
Cut loop wires coming from A16P/X13A/1+4 (factory
mounted)
b
Splicing connectors (field supply)
c
Wires from the brine low pressure switch cable (field
supply)
3
Fix the cable with cable ties to the cable tie mountings.
5.14
LAN adapter
5.14.1
About the LAN adapter
The indoor unit contains an integrated LAN adapter (model:
BRP069A61), which allows for:
▪ App control of the Daikin Altherma heat pump system
▪ Integration of the heat pump system in a Smart Grid application
Components: PCB
X1A
X2A
X3A
X4A
b
a
LD1
LD2
LD3
LD4
X1A~X4A
Connectors
a
DIP switch
b
Status LEDs
Status LEDs
LED
Description
Behaviour
LD1
Indication of power to the
adapter, and of normal
operation.
▪ LED flashing: normal
operation.
▪ LED NOT flashing: no
operation.
LD2
Indication of TCP/IP
communication with the
router.
▪ LED
ON:
normal
communication.
▪ LED
flashing:
communication
problem.
LD3
Indication of
communication with the
indoor unit.
▪ LED
ON:
normal
communication.
▪ LED
flashing:
communication
problem.
LD4
Indication of Smart Grid
activity.
▪ LED ON: Smart Grid
functionality
of
the
indoor unit is controlled
by the LAN adapter.
▪ LED
OFF:
system
operating
in
normal
operation
conditions
(space heating/cooling,
production of domestic
hot water), or running in
the
"Normal
operation"/"Free
running"
Smart
Grid
operation mode.
System requirements
The requirements posed on the Daikin Altherma system depend on
the LAN adapter application/system layout.
App control
Item
Requirement
LAN adapter software It is recommended to ALWAYS keep the
LAN adapter software up-to-date.
Unit control method
On the user interface, make sure to set
[2.9]=2 (
Control
=
Room thermostat
).