SiBE121135
Field Settings
Trial Operation and Field Settings
421
5.3.2 Overview of the Field Settings
: factory set
Note:
1. Any function that is not available on the indoor unit is not displayed.
2.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
10
(20)
0
Filter cleaning sign
interval
Ultra longlife
filter
Li
g
ht
Approx.
10,000 hrs.
He
a
v
y
Approx.
5,000 hrs.
—
—
Longlife filter
Approx.
2,500 hrs.
Approx.
1,250 hrs.
1
Longlife filter type
Longlife filter
Ultra longlife
filter
—
—
2
Remote controller thermistor
Enabled
Disabled
—
—
3
Filter cleaning sign
Display
No display
—
—
11
(21)
0
Indoor unit number of simultaneous
operation system
Pair
Twin
Triple
Double twin
1
Simultaneous operation system
individual setting
Unified setting
Individual
setting
—
—
7
External static pressure setting
Airflow
adjustment is
OFF
Completion of
airflow
adjustment
Start of airflow
adjustment
—
12
(22)
1
Forced ON/OFF function
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential changeover
(setting for when using remote sensor)
1°C
0.5°C
—
—
13
(23)
0
High air outlet velocity (for high ceiling
applications)
≤
2.7 m
2.7 ~ 3.0 m
3.0 ~ 3.5 m
—
1
Selection of airflow direction (setting
for when a blocking pad kit has been
installed)
4-way flow
3-way flow
2-way flow
—
3
Selection of airflow function (setting
for when using a decoration panel for
outlet)
Equipped
Not equipped
—
—
4
Airflow direction range setting
Upper
Normal
Lower
—
6
External static pressure
Refer to Note 2.
14
(24)
2
Dust collection sign interval
Approx. 1,250
hrs.
Approx. 2,500
hrs.
Approx. 5,000
hrs.
—
3
Filter replacement sign
No display
Approx. 32,000
hrs.
Approx. 48,000
hrs.
Approx. 72,000
hrs.
4
Panel indicator (green) ON/OFF
The indicator
lights up during
both air
conditioning
operation and
filter auto-
cleaning.
The indicator
can light up only
during filter
auto-cleaning.
The indicator
does not light
up during both
air conditioning
operation and
filter auto-
cleaning.
—
8
Selection of the automatic control
operation lock mode
ON
OFF
—
—
9
Dust amount setting
Standard
Heavy
—
—
15
(25)
3
Drain pump operation with humidifying
Not equipped
Equipped
—
—
: factory set
External static pressure (Pa)
Mode
No.
First
code No.
Second
code No.
FBQ
35 class 50 class 60 class
13 (23)
6
03
30
30
30
04
35
35
40
05
40
40
50
06
45
45
60
07
50
50
70
08
60
60
80
09
70
70
90
10
80
80
100
11
90
90
—
12
100
100
—