SiBE121135
Troubleshooting for Outdoor Unit
Service Diagnosis
315
7.15 CT or Related Abnormality
Remote
Controller
Display
H8
Outdoor Unit LED
Display
A
j
1
i
2
i
3
h
4
h
5
h
Method of
Malfunction
Detection
A CT or related error is detected by checking the compressor running frequency and CT-
detected input current.
Malfunction
Decision
Conditions
The compressor running frequency is more than
A
Hz and input current is less than
B
A.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Broken or disconnected wiring
Defective reactor
Defective outdoor unit PCB
A
(Hz)
B
(A)
40/50/52/58/68/75 class
55
0.5
80/90 class
32
0.5