Outdoor Unit (80 / 90 Class)
Si12-411A
240
Removal Procedure
1.10 Removal of
Compressor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Remove the terminal
cover.
Be careful to avoid burning
the compressor terminals or
the nameplate.
2
Remove the overload
relay.
3
Disconnect the flag
shape terminal.
As precaution, keep the
contents in memorandum.
4
There is one nut fixing
the compressor.
Remove the nut with a
spanner.