Si12-411A
Outdoor Unit (80 / 90 Class)
Removal Procedure
225
4
Remove the connector
S92
for gas pipe
thermistor.
5
Remove the connector
S90
for thermistor.
Outdoor air
thermistor (Blue)
Discharge pipe
thermistor (Black)
Heat exchanger
thermistor (Gray)
6
Remove the overload
relay connector
S40
.
7
Remove the reactor
lead wire.
Step
Procedure
Points