Si12-411A
Outdoor Unit (80 / 90 Class)
Removal Procedure
223
3
Remove the earth wire.
4
Remove 1 screw of the
terminal board.
5
Release the tab on the
top right of the terminal
board.
6
Pull out the terminal
board and open it.
Glass tube fuse and varistor
cannot be replaced
individually because lead-
free soldering is provided.
Step
Procedure
Points