Outdoor Unit (80 / 90 Class)
Si12-411A
224
Removal Procedure
2. Remove each wire harness
1
Disconnect 4
connectors of the
electronic expansion
valve lead wires.
When reconnecting, make
sure to match the wire to the
correct connector.
2
Remove the four way
valve connector
S80
.
3
Remove the connector
S93
for liquid pipe
thermistor.
Step
Procedure
Points
Connector
Electronic
expansion
valve No.
Harness
length
S20
(White)
EVA
630
S21
(Red)
EVB
730
S22
(Blue)
EVC
825
S23
(Yellow)
EVD
940