48
Figure 5-17 Parameter
Step 2
Configure temperature measurement parameters.
1) Click to add a rule.
2) Double-click the added rule to select measurement items and edit the measurement
name.
3) Draw the rules.
Select
Measurement Items
as
Spot
, and you can click a position on the surveillance
image and a spot is formed.
Select
Measurement Items
as
Line
,
Rectangle
or
Ellipse
, and you can hold the left
mouse button to draw rules that you need on the surveillance image.
Select
Measurement Items
as
Polygon
, and you can hold the left mouse button to
draw rules that you need on the surveillance image. Right-click to end your drawing.
●
You can draw 12 rules at most.
●
Select a rule that you have drawn and click
Redraw Rule
. Then you can delete the
rule and draw a new one.
4) Select the
Open Local Config
checkbox and configure parameters.
Table 5-5 Description of local configuration parameter
Parameters
Description
Target Radiation Coefficient
Radiation coefficient of targets that are shot by this Camera. It
ranges from 0.5 to 1.
Target Distance
Distance from the Camera to targets that are shot. It ranges
from 0 m to 10000 m.
Target Reflection
Temperature
Temperature of targets that are shot by this Camera. It ranges
from–50 °C to +327.7 °C.
5) Select the
Relay-out
checkbox and configure the parameters.