MAIN COMMON FAULTS AND REMOVEL METHODS OF GENSET
Can not start the genset:
When the gas generator can not start, the engine is not working normally. Please check one by one
as the following methods:
1. Basic checking:
•
•
•
Check whether the gas valve open or not, whether with the suitable gas input.
•
•
Check the mains input when starting the unit automatically.
•
Check the power indicator lights up or not.
2. Checking method:
•
reduced. Or turn the transition nut to adjust the pipe area.
•
Battery voltage test: use a multimeter to test the battery voltage, the voltage is 12.6 V, which means
the battery with has power; if the voltage is below 12.6V, the battery can not drive the starting motor.
•
Cylinder wire checking: check it as the picture below, the gap between the conductor and engine is
3-5mm, start the start motor, then there will be spark if ignited.
•
Spark plug checking: Connect the spark plug with land, start the start motor, observe whether the
spark plug discharging to the ground or not, if there is spark, then the spark plug damaged.
•
Igniter checking: use a multimeter to test the socket voltage, which should be 12V.
23
MAIN COMMON FAULTS AND REMOVEL METHODS OF GENSET
Can not start the genset:
When the gas generator can not start, the engine is not working normally. Please check one by one
as the following methods:
1. Basic checking:
•
•
•
Check whether the gas valve open or not, whether with the suitable gas input.
•
•
Check the mains input when starting the unit automatically.
•
Check the power indicator lights up or not.
2. Checking method:
•
reduced. Or turn the transition nut to adjust the pipe area.
•
Battery voltage test: use a multimeter to test the battery voltage, the voltage is 12.6 V, which means
the battery with has power; if the voltage is below 12.6V, the battery can not drive the starting motor.
•
Cylinder wire checking: check it as the picture below, the gap between the conductor and engine is
3-5mm, start the start motor, then there will be spark if ignited.
•
Spark plug checking: Connect the spark plug with land, start the start motor, observe whether the
spark plug discharging to the ground or not, if there is spark, then the spark plug damaged.
•
Igniter checking: use a multimeter to test the socket voltage, which should be 12V.
corresponding positions
MAIN COMMON FAULTS AND REMOVEL METHODS OF GENSET
Can not start the genset:
When the gas generator can not start, the engine is not working normally. Please check one by one
as the following methods:
1. Basic checking:
•
•
•
Check whether the gas valve open or not, whether with the suitable gas input.
•
•
Check the mains input when starting the unit automatically.
•
Check the power indicator lights up or not.
2. Checking method:
•
reduced. Or turn the transition nut to adjust the pipe area.
•
Battery voltage test: use a multimeter to test the battery voltage, the voltage is 12.6 V, which means
the battery with has power; if the voltage is below 12.6V, the battery can not drive the starting motor.
•
Cylinder wire checking: check it as the picture below, the gap between the conductor and engine is
3-5mm, start the start motor, then there will be spark if ignited.
•
Spark plug checking: Connect the spark plug with land, start the start motor, observe whether the
spark plug discharging to the ground or not, if there is spark, then the spark plug damaged.
•
Igniter checking: use a multimeter to test the socket voltage, which should be 12V.
Summary of Contents for DAPD17REQ-EC
Page 26: ...2...
Page 29: ...EN 5 2 1 2 3 4 5 3 DAPD17REQEC 1...
Page 41: ...17 OFF ATS...
Page 42: ...18 E N LPG NG...
Page 45: ...21 9 1 2 3 10 1 2 3 4 11 1 2 3 4 5 6 7 4 5 6 12 1 2 3 13 1 2 14 1 2 3 15 1 2 3...
Page 46: ...22 EN AC AVR...
Page 47: ...23 3 5...
Page 48: ...24 EN 1 2 1 2 12 DC 1 12 70 2 20 DC 200 DC 3 90 1...
Page 49: ......