The emergency stop switch, power switch and fuel switch must keep at open.
The charger must keep in charging condition also.
7. INSPECTION GAS GENERATOR WHEN OPERATING
Inspect the following parts when operating.
1. Radiator (Coolant)
Let the engine cools down, and remove the radiator cap.
runs into the rubber hose after running with high temperature, please shut the generator down to
resolve the problem.
Checklist
:
•
Check for coolant leaks
•
Inspect the inside and outside of the radiator to ensure no excessive dirty or dust.
•
Check the cleanliness of the radiator and ensure no dust, dirty or foreign substance.
•
Check the hose to ensure it is not blocked.
2. Fault indicator lamp
Red lamp occurs the operator to shut the generator down and do the trouble shooting.
If the generator will not start, press the emergency stop switch. Rotate clockwise to pop up. After
waiting for 30 seconds, try to starting again. If the generator cannot be started, check the generator
If after restarting the generator, the fault indicator light is red, the generator will shut down. If this
happens, check the reason for the fault occurring. After correcting the fault, the generator is able to
be re-started. If the fault indicator light remains off, then the generator is operating normally.
the generator.
3. Exhaust color
As long as the generator engine is running within the rated output range,
a. The exhaust will be colorless.
b. If the exhaust is dark grey or black when after running for 60 seconds or more, this is an indica-
tion of a problem. Shut the engine down until the problem is corrected.
4. Other problems requiring shutting down the generator
You should shut down the engine if the following circumstances happen.
•
The engine speed is hunting ( inconsistently speeding up and down).
•
An abnormal noise is heard coming from the generator.
The emergency stop switch, power switch and fuel switch must keep at open.
The charger must keep in charging condition also.
7. INSPECTION GAS GENERATOR WHEN OPERATING
Inspect the following parts when operating.
1. Radiator (Coolant)
Let the engine cools down, and remove the radiator cap.
runs into the rubber hose after running with high temperature, please shut the generator down to
resolve the problem.
Checklist
:
•
Check for coolant leaks
•
Inspect the inside and outside of the radiator to ensure no excessive dirty or dust.
•
Check the cleanliness of the radiator and ensure no dust, dirty or foreign substance.
•
Check the hose to ensure it is not blocked.
2. Fault indicator lamp
Red lamp occurs the operator to shut the generator down and do the trouble shooting.
If the generator will not start, press the emergency stop switch. Rotate clockwise to pop up. After
waiting for 30 seconds, try to starting again. If the generator cannot be started, check the generator
If after restarting the generator, the fault indicator light is red, the generator will shut down. If this
happens, check the reason for the fault occurring. After correcting the fault, the generator is able to
be re-started. If the fault indicator light remains off, then the generator is operating normally.
the generator.
3. Exhaust color
As long as the generator engine is running within the rated output range,
a. The exhaust will be colorless.
b. If the exhaust is dark grey or black when after running for 60 seconds or more, this is an indica-
tion of a problem. Shut the engine down until the problem is corrected.
4. Other problems requiring shutting down the generator
You should shut down the engine if the following circumstances happen.
•
The engine speed is hunting ( inconsistently speeding up and down).
•
An abnormal noise is heard coming from the generator.
The emergency stop switch, power switch and fuel switch must keep at open.
The charger must keep in charging condition also.
7. INSPECTION GAS GENERATOR WHEN OPERATING
Inspect the following parts when operating.
1. Radiator (Coolant)
Let the engine cools down, and remove the radiator cap.
runs into the rubber hose after running with high temperature, please shut the generator down to
resolve the problem.
Checklist
:
•
Check for coolant leaks
•
Inspect the inside and outside of the radiator to ensure no excessive dirty or dust.
•
Check the cleanliness of the radiator and ensure no dust, dirty or foreign substance.
•
Check the hose to ensure it is not blocked.
2. Fault indicator lamp
Red lamp occurs the operator to shut the generator down and do the trouble shooting.
If the generator will not start, press the emergency stop switch. Rotate clockwise to pop up. After
waiting for 30 seconds, try to starting again. If the generator cannot be started, check the generator
If after restarting the generator, the fault indicator light is red, the generator will shut down. If this
happens, check the reason for the fault occurring. After correcting the fault, the generator is able to
be re-started. If the fault indicator light remains off, then the generator is operating normally.
the generator.
3. Exhaust color
As long as the generator engine is running within the rated output range,
a. The exhaust will be colorless.
b. If the exhaust is dark grey or black when after running for 60 seconds or more, this is an indica-
tion of a problem. Shut the engine down until the problem is corrected.
4. Other problems requiring shutting down the generator
You should shut down the engine if the following circumstances happen.
•
The engine speed is hunting ( inconsistently speeding up and down).
•
An abnormal noise is heard coming from the generator.
• Use the multi-meter to check whether the voltage of battery is over 12.6V, charge the battery if the
– Do not open or mutilate the battery. Released electrolyte has been known to be harmful
– A battery presents a risk of electrical shock and high short circuit current. The following
7. After the unit started then can be automatically generation( match with ATS enter into automatical
The emergency stop switch, power switch and fuel switch must keep at open.
The charger must keep in charging condition also.
7. INSPECTION GAS GENERATOR WHEN OPERATING
Inspect the following parts when operating.
1. Radiator (Coolant)
Let the engine cools down, and remove the radiator cap.
runs into the rubber hose after running with high temperature, please shut the generator down to
resolve the problem.
Checklist
:
•
Check for coolant leaks
•
Inspect the inside and outside of the radiator to ensure no excessive dirty or dust.
•
Check the cleanliness of the radiator and ensure no dust, dirty or foreign substance.
•
Check the hose to ensure it is not blocked.
2. Fault indicator lamp
Red lamp occurs the operator to shut the generator down and do the trouble shooting.
If the generator will not start, press the emergency stop switch. Rotate clockwise to pop up. After
waiting for 30 seconds, try to starting again. If the generator cannot be started, check the generator
If after restarting the generator, the fault indicator light is red, the generator will shut down. If this
happens, check the reason for the fault occurring. After correcting the fault, the generator is able to
be re-started. If the fault indicator light remains off, then the generator is operating normally.
the generator.
3. Exhaust color
As long as the generator engine is running within the rated output range,
a. The exhaust will be colorless.
b. If the exhaust is dark grey or black when after running for 60 seconds or more, this is an indica-
tion of a problem. Shut the engine down until the problem is corrected.
4. Other problems requiring shutting down the generator
You should shut down the engine if the following circumstances happen.
•
The engine speed is hunting ( inconsistently speeding up and down).
•
An abnormal noise is heard coming from the generator.
• Use the multi-meter to check whether the voltage of battery is over 12.6V, charge the battery if the
– Do not open or mutilate the battery. Released electrolyte has been known to be harmful
– A battery presents a risk of electrical shock and high short circuit current. The following
7. After the unit started then can be automatically generation( match with ATS enter into automatical
The emergency stop switch, power switch and fuel switch must keep at open.
The charger must keep in charging condition also.
7. INSPECTION GAS GENERATOR WHEN OPERATING
Inspect the following parts when operating.
1. Radiator (Coolant)
Let the engine cools down, and remove the radiator cap.
runs into the rubber hose after running with high temperature, please shut the generator down to
resolve the problem.
Checklist
:
•
Check for coolant leaks
•
Inspect the inside and outside of the radiator to ensure no excessive dirty or dust.
•
Check the cleanliness of the radiator and ensure no dust, dirty or foreign substance.
•
Check the hose to ensure it is not blocked.
2. Fault indicator lamp
Red lamp occurs the operator to shut the generator down and do the trouble shooting.
If the generator will not start, press the emergency stop switch. Rotate clockwise to pop up. After
waiting for 30 seconds, try to starting again. If the generator cannot be started, check the generator
If after restarting the generator, the fault indicator light is red, the generator will shut down. If this
happens, check the reason for the fault occurring. After correcting the fault, the generator is able to
be re-started. If the fault indicator light remains off, then the generator is operating normally.
the generator.
3. Exhaust color
As long as the generator engine is running within the rated output range,
a. The exhaust will be colorless.
b. If the exhaust is dark grey or black when after running for 60 seconds or more, this is an indica-
tion of a problem. Shut the engine down until the problem is corrected.
4. Other problems requiring shutting down the generator
You should shut down the engine if the following circumstances happen.
•
The engine speed is hunting ( inconsistently speeding up and down).
•
An abnormal noise is heard coming from the generator.
• Use the multi-meter to check whether the voltage of battery is over 12.6V, charge the battery if the
– Do not open or mutilate the battery. Released electrolyte has been known to be harmful
– A battery presents a risk of electrical shock and high short circuit current. The following
6. Press 7 or 8, observe the frequency, voltage , speed and the 12V working voltage as well as the
7. After the unit started then can be automatically generation( match with ATS enter into automatical
The emergency stop switch, power switch and fuel switch must keep at open.
The charger must keep in charging condition also.
7. INSPECTION GAS GENERATOR WHEN OPERATING
Inspect the following parts when operating.
1. Radiator (Coolant)
Let the engine cools down, and remove the radiator cap.
runs into the rubber hose after running with high temperature, please shut the generator down to
resolve the problem.
Checklist
:
•
Check for coolant leaks
•
Inspect the inside and outside of the radiator to ensure no excessive dirty or dust.
•
Check the cleanliness of the radiator and ensure no dust, dirty or foreign substance.
•
Check the hose to ensure it is not blocked.
2. Fault indicator lamp
Red lamp occurs the operator to shut the generator down and do the trouble shooting.
If the generator will not start, press the emergency stop switch. Rotate clockwise to pop up. After
waiting for 30 seconds, try to starting again. If the generator cannot be started, check the generator
If after restarting the generator, the fault indicator light is red, the generator will shut down. If this
happens, check the reason for the fault occurring. After correcting the fault, the generator is able to
be re-started. If the fault indicator light remains off, then the generator is operating normally.
the generator.
3. Exhaust color
As long as the generator engine is running within the rated output range,
a. The exhaust will be colorless.
b. If the exhaust is dark grey or black when after running for 60 seconds or more, this is an indica
tion of a problem. Shut the engine down until the problem is corrected.
4. Other problems requiring shutting down the generator
You should shut down the engine if the following circumstances happen.
•
The engine speed is hunting ( inconsistently speeding up and down).
•
An abnormal noise is heard coming from the generator.
14
E
N
خرﭼ و هدرﮐ دﻧﻠﺑ ار هﺎﮕﺗﺳد
ﻧﮐ لﻔﻗ ار ﺎھ
ﯾ د
.
ارﺑ
ی
هﺎﮕﺗﺳد ندرﮐ دﻧﻠﺑ
،
ﻣﯾ
ﻧھآ ﮫﻠ
ﯽ
زا ار
روﺑﻋ ﺎھ خاروﺳ
هداد
ﻧﮐ هدﺎﻔﺗﺳا بﺎﻧط زا و
ﯾد
.
۵
.
رﺗﺎﺑ
ی
رﺳ
ﻔﻧﻣ و (+) تﺑﺛﻣ
ﯽ
)
-
(
رﺗﺎﺑ
ی
ﺳ ﮫﺑ ار
ﯾ
ﻔﻧﻣ و تﺑﺛﻣ م
ﯽ
ﻧﮐ لﺻو
ﯾ
ﺳ ،د
ﯾ
ﻔﻧﻣ م
ﯽ
)
-
رﺧآ ار (
ﯾ
ن
ﮫﻠﺣرﻣ
لﺎﺻﺗا مﺎﮕﻧھ
ﮫﺑ
رﺗﺎﺑ
ی
ﻧﮐ لﺻو
ﯾ
.د
زﺎﮔ روﺗارﻧژ
ی
ﻣﻧ نﺷور
ﯽ
دوﺷ
،
رﺗﺎﺑ رﮔا
ی
دوﺷ لﺻو سوﮑﻌﻣ تروﺻ ﮫﺑ
ﯾﺎ
ﺳآ رادﻣ درﺑ ﮫﺑ تﺳا نﮑﻣﻣ
ﯾ
ب
دوﺷ دراو
.
رﺗﺎﺑ زا هدﺎﻔﺗﺳا زا لﺑﻗ
ی
ﻣﻌﺗ نودﺑ
ﯾ
رادﮭﮕﻧ و ر
ی
ﻣ ،
ﯽ
ﺎﻣزآ ژﺎﺗﻟو ناوﺗ
ﯾ
ش
≤
١٢�۶
تﻟو
ﻘﺗﺳﻣ ار
ﯾ
ﻟوا
زا
سﭘ
.
داد
رارﻗ
هدﺎﻔﺗﺳا
دروﻣ
ًﺎﻣ
ﯾ
ن
هدﺎﻔﺗﺳا
ﯾ
> ﺎ
١٢�۶
تﻟو
ﺎﺑ
ﯾ
ﻧﮐ هدﺎﻔﺗﺳا سﭘﺳ دوﺷ ژرﺎﺷ هرﺎﺑود د
ﯾد
.
Summary of Contents for DAPD17REQ-EC
Page 26: ...2...
Page 29: ...EN 5 2 1 2 3 4 5 3 DAPD17REQEC 1...
Page 41: ...17 OFF ATS...
Page 42: ...18 E N LPG NG...
Page 45: ...21 9 1 2 3 10 1 2 3 4 11 1 2 3 4 5 6 7 4 5 6 12 1 2 3 13 1 2 14 1 2 3 15 1 2 3...
Page 46: ...22 EN AC AVR...
Page 47: ...23 3 5...
Page 48: ...24 EN 1 2 1 2 12 DC 1 12 70 2 20 DC 200 DC 3 90 1...
Page 49: ......