ENGLISH
110
To help the user with the setting, the page shows the dry running factor measured in real time (in addition to the SO minimum dry
running factor to be set). The value measured is shown in a box below the name of the SO parameter and is called “SOm”.
In the multi inverter configuration, SO is a parameter which can be propagated between inverters but it is not a sensitive
parameter, i.e. it does not necessarily have to be the same for all inverters. When a change in SO is measured the user is asked
whether the value should be propagated to all the inverters.
6.5.15
MP: Minimum pressure pump stop due to water failure
This sets the minimum pressure pump stop due to water failure. If the system pressure reaches a pressure below MP the lack of water
is signalled.
This parameter is set on all systems without flow sensor. If the pump functions with flow sensor MP is blocked and disabled.
The MP default value is 0.0 bar and can be set up to 5.0 bar.
If MP=0 (default), the dry running is detected by the flow or the dry running factor SO algorithm;
if MP is not equal to 0, the lack of water is detected when the pressure is below the MP value.
The lack of water alarm is detected only when the pressure goes below the MP value for the amount of time set for the TB value, see
par. 6.6.1.
In the multi inverter configuration, MP is a sensitive parameter therefore it must always be the same along the chain of inverters in
communication and when the value is changed it is automatically propagated to all the inverters.
6.6
Technical Assistance Menu
From the main menu, press and hold “MODE” & “SET” & “+“ simultaneously until “TB” appears on display (or use the b or –
in the selection menu). This menu enables the display and modification of various configuration parameters. The MODE button enables
the user to scroll through the menu pages, while b and – enable respectively to increase and decrease the value of the
parameter concerned. To exit the current menu and return to the main menu, press SET.
6.6.1
TB: Water failure block time
Entry of a water failure block delay time enables selection of the time (in seconds) taken by the inverter to notify of low water levels on
the electric pump.
Modifications to this parameter may be useful if a known delay exists between the moment in which the pump is activated and the
actual moment of supply. One example is that of a system where the electric pump intake line is particularly long and is subject to
small leaks. In this case it may occur that the pipeline empties, and even if the water supply is regular, the electric pump takes some
time to reload, deliver flow and pressurise the system.
6.6.2
T1: Shutdown time after low pressure signal
This sets the inverter shutdown time starting from reception of the low pressure signal (see Impostazione della rilevazione di bassa
pressione par 6.6.13.5). The low pressure signal may be received on any of the 4 inputs, by suitably configuring the input (Setup degli
ingressi digitali ausiliari IN1, IN2, IN3, IN4 par 6.6.13).
T1 can be set between 0 and 12 s. The default setting is 2 s.
6.6.3
T2: Shutdown delay
This sets the delay after which the inverter shuts down after shutdown conditions have been reached: system pressure and flow at
minimum values.
T2 can be set between 5 and 120 s. The default setting is 10 s.
6.6.4
GP: Proportional gain coefficient
The proportional gain should generally be increased for elastic systems (wide and PVC pipelines) and reduced in the case of rigid
systems (narrow and steel pipelines).
To maintain constant system pressure, the inverter performs a PI check on the measured pressure error. On the basis of this error,
the inverter calculates the power to supply to the electric pump. The behaviour of this check depends on the set parameters GP and
GI. To meet the different requirements of the various types of hydraulic systems where the system may operate, the inverter enables
the selection of parameters that are different from the default settings.
On virtually all systems, the factory setting of parameters
GP and GI are optimal.
However, in the event of problems with regulation, these settings may be modified as required.
Summary of Contents for AD 1.0 AC
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 74: ...ENGLISH 72 Figure 2 Fixture and minimum clearance for air circulation...
Page 135: ...FRAN AIS 133 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 196: ...DEUTSCH 194 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 257: ...ESPA OL 255 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 269: ...ESPA OL 267 Figura 13 Ejemplo de conexi n de las entradas...
Page 312: ...310 IEC 60634 1...
Page 313: ...311 1 6 1 1...
Page 317: ...315 1 2 1 1 1 1 2 5 2 1 2 1 2 2...
Page 318: ...316 2...
Page 319: ...317 2 2 3 3 15 2 2 1 1a 2a...
Page 320: ...318 4a 5b 1b 127 240 240 480 3 6 3b...
Page 324: ...322 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 332: ...330 3 14 64 X 128 4 MODE SET 12 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 333: ...331 3 2 1 2 3 2 1 MODE SET MODE 10 2 2 5 5 5 2 2 12...
Page 335: ...333 3 2 2 13 SET 15 15 14 16...
Page 337: ...335 17 15 15 3 4 PW 6 6 16 GO SB...
Page 338: ...336 4 4 1 Link 8 4 2 4 2 1 Link Link 16 18 Link...
Page 367: ...365 OC 10 6 OF 10 6 33 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 379: ...NEDERLANDS 377 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 440: ...SVENSKA 438 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 501: ...T RK E 499 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 556: ...554 IEC 364 1 inverter...
Page 557: ...555 1 Inverter inverter inverter 6 inverter 1 1...
Page 561: ...559 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 562: ...560 2...
Page 563: ...561 2 2 3 3 inverter 15 inverter 2 2 1 inverter inverter 1a 2a...
Page 564: ...562 4a 5b 1b V 127 240 240 480 mm 3 6 3b azione...
Page 568: ...566 2 2 2 inverter inverter GP GI 6 6 4 6 6 5 inverter 8 A B C D...
Page 576: ...574 3 14 oled 64 X 128 4 MODE SET 12 inverter 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 577: ...575 3 2 1 2 3 2 1 MODE SET Setpoint MODE 10 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 12...
Page 581: ...579 17 15 15 3 4 Password inverter password password inverter password PW 6 6 16 GO SB FAULT...
Page 623: ...ROM N 621 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 684: ...POLSKI 682 Rys 2 Mocowanie oraz minimalna odleg o na potrzeby cyrkulacji powietrza...
Page 745: ...MAGYAR 743 2 bra R gz t s s minim lis t vols g a szell z leveg kering se rdek ben...
Page 800: ...798 IEC 364 1...
Page 801: ...799 1 3 1 1...
Page 805: ...803 1 2 1 1 1 1 2 5 2 1 2 1 2 C...
Page 806: ...804 2...
Page 807: ...805 2 2 3 3 15 2 2 1 1 2a...
Page 808: ...806 4a 5b 1b V 127 240 240 480 3 6 3b...
Page 812: ...810 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 817: ...815 V 36 36 12V A 3 3 3 3 2 13 9 11 8 13...
Page 819: ...817 3 14 64 X 128 4 MODE SET and 12 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 820: ...818 3 2 1 2 3 2 1 10 2 2 5 5 5 2 2 12...
Page 824: ...822 15 3 4 GO SB FAULT...
Page 825: ...823 4 4 1 8 4 2 4 2 1 16 18...
Page 862: ...ESKY 860 Obr zek 2 P ipevn n a minim ln vzd lenost kv li cirkulaci vzduchu...
Page 917: ...915 IEC 60634 1...
Page 918: ...916 1 6 1 1...
Page 922: ...920 1 2 1 1 1 1 2 5 2 1 2 1 2 2...
Page 923: ...921 2...
Page 924: ...922 2 2 3 3 15 2 2 1 1a 2a...
Page 925: ...923 4a 5b 1b 127 240 240 480 3 6 3b...
Page 929: ...927 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 931: ...929 10 4 20 6 4 20 PR 6 5 7 4 20 2 18 J5 GND 1 J5 GND o IN 11 J5 4 20 7 OUT 8 10 11 IN...
Page 935: ...933 13 J5 I1 11 17 16 18 16 17 I2 11 15 16 18 15 16 I3 11 14 13 18 13 14 I4 11 12 13 8 12 13 9...
Page 937: ...935 3 14 64 X 128 4 MODE SET 12 9 MODE 1 SET 10 3 EEprom SET 6 SET MODE 3 1 11...
Page 938: ...936 3 2 1 2 3 2 1 MODE SET MODE 10 2 2 5 5 5 2 2 11...
Page 940: ...938 3 2 2 13 SET 15 15 14 16...
Page 942: ...940 17 14 15 3 4 PW 6 6 16 GO SB FAULT...
Page 943: ...941 4 4 1 Link 8 4 2 4 2 1 Link Link 16 18 Link...
Page 946: ...944 4 3 1 2 1 4 3 1 3 SET MODE LA RC MS FS SO AE O1 1 O2 2 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL...
Page 969: ...967 10 0 Mode Set PW 0 PW 2 7 3 6 6 16 1 PW PW PW PW 0 PW 0 0 PW PW PW PW PW 0 PW...