
ENGLISH
109
Table of correspondence of diameters and k-factors for flow sensor F3.00
Pipe diameter [inch]
Internal DN pipe
diameter [mm]
K-factor
Minimum flow l/min
Maximum flow
l/min
1/2
15
225,0
1,6
85
3/4
20
142,0
2,8
151
1
25
90,0
4,4
236
1 1/4
32
60,7
7,2
386
1 1/2
40
42,5
11,3
603
2
50
24,4
17,7
942
2 1/2
65
15,8
29,8
1592
3
80
11,0
45,2
2412
3 1/2
90
8,0
57,2
3052
4
100
6,1
70,7
3768
5
125
4,0
110,4
5888
6
150
2,60
159,0
8478
8
200
1,45
282,6
15072
10
250
0,89
441,6
23550
12
300
0,60
635,9
33912
14
350
0,43
865,5
46158
16
400
0,32
1130,4
60288
18
450
0,25
1430,7
76302
20
500
0,20
1766,3
94200
24
600
0,14
2543,4
135648
Table 22:
Diameter of pipelines, FK conversion factor, minimum and maximum admissible flow
CAUTION: always refer to the manufacturer’s installation notes and compatibility of electric parameters of the flow sensor and those
of the inverter, as well as exact correspondence of connections. Incorrect settings will cause false flow readings with possible undesired
shutdown or continuous operation without stops.
6.5.12
FZ: Setting zero flow frequency
It expresses the frequency below which it may be considered that there is zero flow in the system.
It can be set only if FI has been set to operate without a flow sensor. If FI has been set to operate with a flow sensor, the parameter
FZ is blocked. The parameter disabled message is indicated by an icon showing a padlock.
If FZ = 0 Hz is set the inverter will use the self-adaptive operating mode
, instead if FZ ≠ 0
Hz is set then the inverter will use the
minimum frequency operating mode (see par. 6.5.9.1).
6.5.13
FT: Shutdown threshold setting
This sets a minimum flow threshold, below which, if there is pressure, the inverter stops the electric pump.
This parameter is used in both operation with and without flow sensor, but the two parameters are different; therefore even when the
setting of FI is changed, the FT value remains consistent with the type of operating mode without overwriting the two values. In
operation with the flow sensor, the FT parameter is in litres/minute or gal/min, while without the flow sensor the value is adimensional.
In the same page, as well as the flow shutdown setting FT, the measured flow rate is displayed, to facilitate user operations. This
appears in a highlighted box below the name of the FT parameter, and bears the text "fl". In operating mode without flow sensor, the
minimum flow “fl” displayed in the box is not immediately available, and may take a few minutes of operation for the figure to be
calculated.
CAUTION: if an excessively high FT value is set, undesired shutdown may occur; if the value is too low operation may be continuous
without stops.
6.5.14
SO: Dry running factor
This sets the minimum dry running factor threshold below which the lack of water is detected. The dry running factor is a non-
dimensional parameter obtained by combining absorbed current and the pump power factor. Thanks to this parameter it is possible to
correctly establish when there is air in the impeller of a pump or if the suction flow is interrupted.
This parameter is used on all multi inverter systems and on all systems without flow sensor. If the pump functions only with one inverter
and flow sensor SO is blocked and disabled.
Summary of Contents for AD 1.0 AC
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 74: ...ENGLISH 72 Figure 2 Fixture and minimum clearance for air circulation...
Page 135: ...FRAN AIS 133 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 196: ...DEUTSCH 194 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 257: ...ESPA OL 255 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 269: ...ESPA OL 267 Figura 13 Ejemplo de conexi n de las entradas...
Page 312: ...310 IEC 60634 1...
Page 313: ...311 1 6 1 1...
Page 317: ...315 1 2 1 1 1 1 2 5 2 1 2 1 2 2...
Page 318: ...316 2...
Page 319: ...317 2 2 3 3 15 2 2 1 1a 2a...
Page 320: ...318 4a 5b 1b 127 240 240 480 3 6 3b...
Page 324: ...322 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 332: ...330 3 14 64 X 128 4 MODE SET 12 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 333: ...331 3 2 1 2 3 2 1 MODE SET MODE 10 2 2 5 5 5 2 2 12...
Page 335: ...333 3 2 2 13 SET 15 15 14 16...
Page 337: ...335 17 15 15 3 4 PW 6 6 16 GO SB...
Page 338: ...336 4 4 1 Link 8 4 2 4 2 1 Link Link 16 18 Link...
Page 367: ...365 OC 10 6 OF 10 6 33 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 379: ...NEDERLANDS 377 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 440: ...SVENSKA 438 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 501: ...T RK E 499 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 556: ...554 IEC 364 1 inverter...
Page 557: ...555 1 Inverter inverter inverter 6 inverter 1 1...
Page 561: ...559 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 562: ...560 2...
Page 563: ...561 2 2 3 3 inverter 15 inverter 2 2 1 inverter inverter 1a 2a...
Page 564: ...562 4a 5b 1b V 127 240 240 480 mm 3 6 3b azione...
Page 568: ...566 2 2 2 inverter inverter GP GI 6 6 4 6 6 5 inverter 8 A B C D...
Page 576: ...574 3 14 oled 64 X 128 4 MODE SET 12 inverter 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 577: ...575 3 2 1 2 3 2 1 MODE SET Setpoint MODE 10 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 12...
Page 581: ...579 17 15 15 3 4 Password inverter password password inverter password PW 6 6 16 GO SB FAULT...
Page 623: ...ROM N 621 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 684: ...POLSKI 682 Rys 2 Mocowanie oraz minimalna odleg o na potrzeby cyrkulacji powietrza...
Page 745: ...MAGYAR 743 2 bra R gz t s s minim lis t vols g a szell z leveg kering se rdek ben...
Page 800: ...798 IEC 364 1...
Page 801: ...799 1 3 1 1...
Page 805: ...803 1 2 1 1 1 1 2 5 2 1 2 1 2 C...
Page 806: ...804 2...
Page 807: ...805 2 2 3 3 15 2 2 1 1 2a...
Page 808: ...806 4a 5b 1b V 127 240 240 480 3 6 3b...
Page 812: ...810 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 817: ...815 V 36 36 12V A 3 3 3 3 2 13 9 11 8 13...
Page 819: ...817 3 14 64 X 128 4 MODE SET and 12 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 820: ...818 3 2 1 2 3 2 1 10 2 2 5 5 5 2 2 12...
Page 824: ...822 15 3 4 GO SB FAULT...
Page 825: ...823 4 4 1 8 4 2 4 2 1 16 18...
Page 862: ...ESKY 860 Obr zek 2 P ipevn n a minim ln vzd lenost kv li cirkulaci vzduchu...
Page 917: ...915 IEC 60634 1...
Page 918: ...916 1 6 1 1...
Page 922: ...920 1 2 1 1 1 1 2 5 2 1 2 1 2 2...
Page 923: ...921 2...
Page 924: ...922 2 2 3 3 15 2 2 1 1a 2a...
Page 925: ...923 4a 5b 1b 127 240 240 480 3 6 3b...
Page 929: ...927 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 931: ...929 10 4 20 6 4 20 PR 6 5 7 4 20 2 18 J5 GND 1 J5 GND o IN 11 J5 4 20 7 OUT 8 10 11 IN...
Page 935: ...933 13 J5 I1 11 17 16 18 16 17 I2 11 15 16 18 15 16 I3 11 14 13 18 13 14 I4 11 12 13 8 12 13 9...
Page 937: ...935 3 14 64 X 128 4 MODE SET 12 9 MODE 1 SET 10 3 EEprom SET 6 SET MODE 3 1 11...
Page 938: ...936 3 2 1 2 3 2 1 MODE SET MODE 10 2 2 5 5 5 2 2 11...
Page 940: ...938 3 2 2 13 SET 15 15 14 16...
Page 942: ...940 17 14 15 3 4 PW 6 6 16 GO SB FAULT...
Page 943: ...941 4 4 1 Link 8 4 2 4 2 1 Link Link 16 18 Link...
Page 946: ...944 4 3 1 2 1 4 3 1 3 SET MODE LA RC MS FS SO AE O1 1 O2 2 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL...
Page 969: ...967 10 0 Mode Set PW 0 PW 2 7 3 6 6 16 1 PW PW PW PW 0 PW 0 0 PW PW PW PW PW 0 PW...