CyberPower Remote Management System
34
bypasshvlimit
10 | 15
Set high bypass voltage in percentage. If the utility
voltage exceeds thresholds, the UPS will be forbidden to
enter Bypass mode.
bypasslvlimit
10 | 15 | 20
Set low bypass voltage in percentage. If the utility voltage
exceeds thresholds, the UPS will be forbidden to enter
Bypass mode.
rechargedelay
0 | 60 | 120 | 180 | 300 | 600 |
1200 | 1800 | 3600
Set the recharge delay in seconds. When the utility power
restores, the UPS will start to recharge until the specified
delay is expired before restoring output power.
rechargecap
0 | 15 | 30 | 45 | 60 | 75 | 90
Set the recharge capacity in percentage. When the utility
power restores, the UPS will start to recharge until the
specified battery capacity is met before restoring output
power.
workmode
normal | eco10% | eco15% |
generator | bypass
normal
-
Normal working mode of the UPS.
eco10%
-
On-line UPS enters Economy 10% mode.
eco15%
-
On-line UPS enters Economy 15% mode.
generator
-
If the UPS uses generator as its input power,
this option should enable the UPS to function normally. If
this option is selected, the UPS will be forbidden to enter
Bypass mode to protect the powered equipment.
bypass
-
Determines whether to allow the UPS to enter
Manual Bypass mode. If this option is enabled, the UPS
will be forced to enter Bypass mode.
returndelay
0 ~ 600
When the utility power restores, the UPS will start to
recharge until the specified delay is expired before
restoring output power. The numbers in the range 1 to
600 seconds are numbers divisible by 5.
Example 1:
To view the available value voltage this UPS output power can be set.
CyberPower >
upscfg supply?
100
110
115
Example 2:
To define bypass condition as check utility voltage only
CyberPower >
upscfg bypasscond voltonly
Example 3:
To define UPS recharge delay as 2 minutes
CyberPower >
upscfg rechargedelay 120