bypasshvlimit 

10 | 15 

Set  high  bypass  voltage  in  percentage.  If  the  utility 

voltage exceeds thresholds, the UPS will be forbidden to 

enter Bypass mode. 

bypasslvlimit 

10 | 15 | 20 

Set low bypass voltage in percentage. If the utility voltage 

exceeds  thresholds,  the  UPS  will  be  forbidden  to  enter 

Bypass mode. 

rechargedelay 

0 | 60 | 120 | 180 | 300 | 600 | 

1200 | 1800 | 3600 

Set the recharge delay in seconds. When the utility power 

restores, the UPS will start to recharge until the specified 

delay is expired before restoring output power. 

rechargecap 

0 | 15 | 30 | 45 | 60 | 75 | 90 

Set the recharge capacity in percentage. When the utility 

power  restores,  the  UPS  will  start  to  recharge  until  the 

specified  battery  capacity  is  met  before  restoring  output 

power. 

workmode 

normal | eco10% | eco15% | 

generator | bypass 

normal

Normal working mode of the UPS.

 

eco10%

On-line UPS enters Economy 10% mode.

 

eco15%

On-line UPS enters Economy 15% mode.

 

generator

If the UPS uses generator as its input power, 

this option should enable the UPS to function normally. If 

this option is selected, the UPS will be forbidden to enter 

Bypass mode to protect the powered equipment.

 

bypass

Determines whether to allow the UPS to enter 

Manual Bypass mode. If this option is enabled, the UPS 

will be forced to enter Bypass mode. 

returndelay 

0 ~ 600 

When  the  utility  power  restores,  the  UPS  will  start  to 

recharge  until  the  specified  delay  is  expired  before 

restoring  output  power.  The  numbers  in  the  range  1  to 

600 seconds are numbers divisible by 5.   

Example 1: 

 

To view the available value voltage this UPS output power can be set. 

 

CyberPower > 

upscfg supply?

 

 

 

100 

 

 

110 

 

 

115 

Example 2: 

 

To define bypass condition as check utility voltage only 

 

CyberPower > 

upscfg bypasscond voltonly

 

Example 3: 

 

To define UPS recharge delay as 2 minutes 

 

CyberPower > 

upscfg rechargedelay 120

 

Summary of Contents for RMCARD205

Page 1: ...Systems Inc All rights reserved K01 E000001 05 User s Manual The Remote Management Card allows a UPS system and environmental sensor to be managed monitored and configured Remote Management Card RMCA...

Page 2: ...CARD Firmware Upgrade 47 Save and Restore Configuration Settings 50 Troubleshooting 51 Conformance Approvals 52 Appendix 1 IP Address Settings for CyberPower Remote Management Card 53 Appendix 2 How t...

Page 3: ...the UPS via serial connection Trigger servers workstations to shutdown during a power event to prevent data loss or corruption Schedule shutdown start up reboot of the UPS remotely Event logging to t...

Page 4: ...r SSH client Optional NMS Network Management System compliant with SNMP Application Unpacking Inspect the Remote Management Card upon receipt The package should contain the following CyberPower Remote...

Page 5: ...to the Network or the Remote Management Card power is off On Yellow The Remote Management Card is connected to the Network Tx Rx LED Off The Remote Management Card power is off On Green The Remote Ma...

Page 6: ...remove the cover 2 Install the CyberPower Remote Management Card into the expansion slot 3 Insert and tighten the retaining screws 4 Connect an Ethernet cable to the Ethernet port of the CyberPower Re...

Page 7: ...n completes run the Power Device Network Utility 3 The main window of the Power Device Network Utility program is shown in Figure 1 The configuration tool will display all CyberPower Remote Management...

Page 8: ...2 168 20 177 and the default Subnet Mask is 255 255 255 0 Figure 2 The Device Network setting window 6 Modify the IP subnet mask or gateway address Enter the new addresses into the corresponding field...

Page 9: ...ique MAC address Note The MAC address is labelled on the card 2 Use the ARP command to set the IP address Example To assign the IP Address 192 168 10 134 for the Remote Management Card which has a MAC...

Page 10: ...t a time Web Content Note English is the default language and you can change to a preferred language Summary Provide an overview of the system operation and the items that are auto refreshed However d...

Page 11: ...he current status of the output power the UPS is supplying to connected equipment Voltage The output voltage the UPS is supplying to the connected equipment Frequency The output frequency the UPS is s...

Page 12: ...as not been set it is recommended that it be set immediately NCL Bank The amount of Non Critical Load banks Extended Battery Modules The amount of the external battery modules connected to the UPS The...

Page 13: ...this option is enabled the UPS will be forced to enter Bypass Mode Bypass Note The UPS may automatically enter Bypass Mode per these configured settings Bypass Condition No Bypass If this option is se...

Page 14: ...es support the Smart Battery Management SBM feature SBM carries out battery tests even if Periodical Battery Test setting is disabled System Cold Start Set the ability of the UPS to start in the absen...

Page 15: ...Delay When utility power is restored the UPS will restore the output of this NCL outlet bank after the delay time is met This prevents excessive power consumption caused by all the connected equipment...

Page 16: ...e of the last battery test Click the Start button to begin a battery test The information will be reported after a battery test completes Note N A means the UPS model does not have this function Last...

Page 17: ...one time event for the UPS to shutdown restart Daily Set a daily re occurrence for the UPS to shutdown restart Weekly Set a weekly re occurrence for the UPS to shutdown restart 1 Click Once Daily or W...

Page 18: ...nitored and controlled to achieve the best energy performance under the EnergyWise operation framework Item Definition Configuration Version The version of EnergyWise supported EnergyWise Enable CISCO...

Page 19: ...al sensor Location The location of the environmental sensor Temperature Current Value The current environmental temperature Maximum The highest temperature and time detected by the environmental senso...

Page 20: ...status or environmental status Input min V The minimum input voltage of the utility power from the previous record Input max V The maximum input voltage of the utility power from the previous record I...

Page 21: ...many events are recorded before it is full Item Definition Event Logs Clear All Logs Clear the existing event logs The Number of Events The number of the existing event logs and the maximum number of...

Page 22: ...Time Configuration Time Zone Choose the RMCARD time zone in GMT Greenwich Mean Time Using NTP server Enter the IP address domain name of NTP servers and set the frequency to update the date and time...

Page 23: ...ore information please refer to Appendix 4 System Security Local Account This page is used to configure the login account Information Description Administrator Administrator has full access to read wr...

Page 24: ...r LDAP server the Remote Management Card can use user name and password that set on the LDAP server to login Item Definition LDAP Server The IP address of LDAP server LDAP SSL Enable to communicate wi...

Page 25: ...Control The IPv6 address is assigned through one of the following methods as configured in the router settings Stateless Address Auto configuration Stateless DHCPv6 or Stateful DHCPv6 Manual The IPv6...

Page 26: ...cy Password The password used to generate the key used for encryption The field must be 16 to 31 characters in length IP Address NMS access can be restricted by entering a specific IP address or an IP...

Page 27: ...P IP port that Telnet or SSH uses to communicate Item Definition Access Allow Access Enable the access to Telnet or SSH version 2 which encrypts transmission of user names passwords and data Telnet Se...

Page 28: ...specific mobile phone number An available SMS service provider is needed System Notifications SMTP Server After setting the proper SMTP server event notification email can be sent to recipients when s...

Page 29: ...between mobile devices The system provides 4 methods for users to choose how they want to send the messages Information Description Service provider is Clickatell Select the Clickatell option in the...

Page 30: ...d by the relevant content before the message is sent by the SMS provider For example Address sample cyberpower com Subject TestSubject Content E_PHONE_NUMBER text E_MESSAGE System Notifications SMS Re...

Page 31: ...rsion installed on the Remote Management Card Firmware Updated Date The last date the firmware was updated MAC Address MAC address of the Remote Management Card Save Configuration Click Save to save t...

Page 32: ...use telnet access command line interface Step 1 Need to make sure the computer has access to the RMCARD installed network At a command prompt type telnet and the IP address for the RMCARD for example...

Page 33: ...nd Line Interface While using the command line interface you can also do the following 1 To close the connection to the command line interface Type exit and press Enter 2 To switch mode as Menu Mode T...

Page 34: ...attery Replacement Date 10 08 2018 NCL Bank 1 Extended Battery Pack 4 upsctrl Description Enable to use UPS Master Switch Option Argument Description reboot off delay reboot duration eg 10 10 off dela...

Page 35: ...y and also saves more battery power High sensitivity allows the UPS to supply the more stable power to equipment and switches to battery mode frequently hvlimit high threshold in VAC When the utility...

Page 36: ...normal Normal working mode of the UPS eco10 On line UPS enters Economy 10 mode eco15 On line UPS enters Economy 15 mode generator If the UPS uses generator as its input power this option should enable...

Page 37: ...ery runtime calibration CyberPower upsbatt cal start date Description Show and configure timezone date format date time Option Argument Description show Display system date information for RMCARD time...

Page 38: ...pdate now 1 8760 now Choose Update right now to update immediately 1 8760 Set the frequency to update the date and time from NTP server Example 1 To enable NTP server define date and time of RMCARD Cy...

Page 39: ...ate 03 08 2015 MAC Address 00 0C 15 00 B9 42 Example 2 To reset RMCARD to default parameter CyberPower sys reset all dst Description Show and configure type of Daylight Saving Time Option Argument Des...

Page 40: ...agement Card with user name and password for authenticate with RADIUS server first If the RADIUS server fails to respond the user name and password that configured in Local Account will be used radius...

Page 41: ...Set user password of admin device Example 1 To define primary admin manager IP as 192 168 26 0 24 CyberPower admin pmip 192 168 26 0 24 Input admin password cyber Pass radius Description Show and con...

Page 42: ...server IP Set the IP address of primary secondary LDAP server prissl secssl enable disable Enable or disable using LDAPS priport secport LDAP server port Set the TCP port which is used by the primary...

Page 43: ...tion for RMCARD dhcp enable disable Enable or disable DHCP dns manual auto Auto Obtain DNS Address from DHCP when DHCP enable Manual Obtain DNS Address by manual when DHCP enable ip system IP Set IP A...

Page 44: ...scription show Display SNMPv1 status for RMCARD access enable disable Enable or disable SNMPv1 snmpv3 Description Show and configure status of SNMPv3 Option Argument Description show Display SNMPv3 st...

Page 45: ...Description Show and configure FTP access type and TCP IP port of FTP Option Argument Description show Display all FTP information for RMCARD access enable disable Enable or disable FTP server port f...

Page 46: ...e disable Enable or disable syslog facility kernel user mail system auth1 syslog link news uucp clock1 auth2 ftp ntp logaudit logalert clock2 local0 local1 local2 local3 local4 local5 local6 local7 Se...

Page 47: ...26 33 Syslog Server Port 514 Example 2 To view information of syslog CyberPower syslog show Syslog Enable Facility Code user Server1 IP 192 168 26 33 Port 514 menumode Description Switch mode as Menu...

Page 48: ...ARD305 1 Remove the card from the UPS without turning the UPS ATS PDU off 2 Remove the jumper from the reset pins as illustrated Do not dispose of the jumper 3 Insert the card into the expansion port...

Page 49: ...turn the UPS off when processing the Firmware upgrade Method 1 Using FTP command Use the following steps to upgrade the firmware 1 Download the latest firmware 2 Extract the downloaded files to C 3 Op...

Page 50: ...used to search the local network subnet again Note You can click View to select the items you want to view Figure 6 The main window of the Upgrade and Configuration Utility program 4 Check the boxes...

Page 51: ...Figure 7 The File Locations of Firmware Data window 7 Click Yes to start firmware upgrade on selected devices as shown in Figure 8 Figure 8 Confirm Upgrade Firmware message window 8 If the firmware u...

Page 52: ...e device configuration to your local PC on the System About To save the configuration file click Save to save the configuration to your local PC The text file will have a default format of YYYY_MM_DD_...

Page 53: ...Management Card 2 If the PC being used is on a different network subnet from the Remote Management Card verify the setting of subnet mask and the IP address of gateway Lost the user name and password...

Page 54: ...ser will be required to correct the interference at his own expense Any special accessories needed for compliance must be specified in the instruction This device complies with part 15 of the FCC Rule...

Page 55: ...le IP address Procedures to find an IP address 1 Locate the subnet of the CyberPower Remote Management Card One way to determine the range of possible IP addresses is to view the network configuration...

Page 56: ...the network using the same IP Address run Ping 192 168 20 240 at the DOS Mode prompt when the IP Address you would like to set is 192 168 20 240 If the response is presented as below the IP address is...

Page 57: ...ignated outlets For example Cyber Outlets 1 2 5 allows the user to control outlets 1 2 and 5 The example of the Dictionary File VENDOR Cyber 3808 BEGIN VENDOR Cyber ATTRIBUTE Cyber Service Type 1 inte...

Page 58: ...a FTP 1 Turn off the UPS 2 Extract the update file to C 3 Open a command prompt window 4 Login to the CyberPower Remote Management Card with FTP command in the command prompt type 1 ftp 2 ftp open 3 T...

Page 59: ...Power com and go to the software section for free download Communicate with PowerPanel Business Edition Client The remote management card requires to authenticate with PowerPanel Business Edition Clie...

Page 60: ...r Windows OS For Linux Operating System please use PowerPanel Business Edition Client software to scan and obtain the IP address To do this go to Power Configuration on the PowerPanel Business Edition...

Page 61: ...e front panel to the card and remove the RMCARD205 front panel Step 2 Screw on the RMCARD305 front panel to the card Step 3 Insert the card into the adapter Ensure that the card is securely seated in...

Page 62: ...Systems Inc www cyberpower com For USA and Canada 4241 12th Ave East Suite 400 Shakopee MN 55379 Toll free 877 297 6937 For all other regions Please visit our website for local contact information K01...

Reviews: