CyberPower Remote Management System
12
Recharged Capacity
When utility power restores, the UPS will start to recharge until the
specified battery capacity is met before restoring output power.
Returned Delay
The Returned Delay will take effect every time when the UPS is turned on.
Line Stable Delay
When the UPS is in Battery Mode and utility power is restored, the UPS
will wait for the specific delay time to change Battery Mode to Line Mode.
When the UPS battery is lower than the Low Battery Threshold and utility
power is restored, the UPS will return to Line Mode immediately.
Battery
Low Battery Threshold
When the UPS supplies battery power and the remaining capacity is lower
than this threshold, the UPS will sound an alarm.
External Battery
Modules
Set the amount of external battery modules. This allows for an accurate
runtime estimation based upon the total number of batteries connected to
the UPS.
Periodical Battery Test
The UPS will cyclically perform the battery test automatically to ensure the
batteries have full functional.
Note:
Only Online (OL) series support the Smart Battery
Management (SBM) feature. SBM carries out battery tests,
even if Periodical Battery Test setting is disabled.
System
Cold Start
Set the ability of the UPS to start in the absence of input power. When this
option is enabled, the UPS can be turned on with battery power.
Audible Alarm
If this option is enabled, the UPS will issue an audible alarm when
supplying battery power, when output is overloaded, or other conditions
are present (varies by UPS model).
Dry Relay Function
This configures the UPS dry relay to function when the selected condition
occurs. Refer to the UPS manual for further information about advanced
UPS dry relay functions. The Dry Relay Function can be configured to be
activated under the following power conditions:
(1) Utility Failure: The utility power fails and the UPS is using battery
power.
(2) Low Battery: The battery capacity is too low to support the connected
computers to shut down.
(3) Alarm: The UPS is issuing the audible alarm due to the occurrence of
warning events, such as overload.
(4) Bypass: The UPS has switched to Bypass Mode.
(5) UPS Fault: The UPS could be malfunctioning due to hardware fault.
Screen Save Time
When no UPS button is pressed and no power event occurs during this
time, the LCD screen will go to sleep.