LCD Setting Configuration Cont.
Silencing Audible Alarms
1. Press any of the four function buttons on the LCD module.
Note:
Battery Low
” condition. This condition will still result in an
audible alarm.
2. Change the “
Audible Alarms
” option to “
Disable
” in the LCD screen and it will no long give an audible
alarm for any malfunction.
Manual Battery Test
Select “
Activate
” in the “
Battery Test
” option of the LCD screen and the unit will perform a manual
battery test.
CONFIGURE
SUBMENU
AVAILABLE SETTINGS
DEFAULT SETTING
USING THE UPS SYSTEM CONT.
1
This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
2
UPS has no bypass when Generator Mode is enabled.
3
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
4
The Low Battery threshold setting will only affect the warning of Power Management Software (PowerPanel® Business) and RMCARD interface.
5
If function is disabled, the Smart Battery Management (SBM) carries out battery tests when certain operating conditions are met.
[Disable] [EPO] [ROO]
Sets [EPO] (Emergency Power Off) to shutdown the UPS
remotely when the contact is open.
Sets [ROO] (Remote On/Off) to turn On the UPS
remotely when the contact is close and turn Off the UPS
remotely when the contact is open. The On/Off power button
on front panel will be disable when set to [ROO].
[Disable] [Enable]
Sets [Disable] or [Enable] to constantly monitor the charger function.
[Disable] [Enable]
Sets [Enable] when UPS install with transformer.
[Disable] [Enable]
Sets [Enable] to active Backfeed connector function.
[Activate?]
Manually reset the Battery Replacement date.
[Mode:DHCP] [Mode:Manual]
[IP Address] [Subnet Mask] [Gateway] (for [Mode:Manual])
Select [Mode:Manual] to set [IP Address] [Subnet Mask]
[Gateway] to network interface (RMCARD) or select DHCP to set
automatically.
[Activate?]
Reset Load Energy Consumption (KWH) value.
Threshold= [20%][25%] [30%][35%]……[55%][60%][65%]
Threshold= [0min][1min][2min][3min]..….[29min][30min]
Signal Inputs
Charger Check
With Transformer
Backfeed Check
Reset ReplaceBAT
IP Address
Reset Load Energy
LowBat Capacity
4
LowBat Runtime
4
Period Battery Test
Disable
Disable
Disable
Disable
None
Mode:DHCP
None
None
20%
5min
Disable
[Disable
5
][1 Weeks][2 Weeks] [3 Weeks] [4 Weeks]