27
USING THE UPS SYSTEM CONT.
LCD Setting Configuration Cont.
CONFIGURE
SUBMENU
AVAILABLE SETTINGS
DEFAULT SETTING
ECO Mode
1
[Disable] [Enable]
Disable
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
When ECO mode is enabled the UPS will check the
following specifications of Bypass quality
(1) Bypass voltage is inside the [V Range= +/-10%]
(default setting) or [V Range= +/-15%].
(2) Bypass frequency is inside the +/-3Hz range of
output nominal frequency.
V Range= +/-10%
Manual Bypass
[Disable] [Enable]
When performing UPS maintenance, the user
can manually transfer the connected load to
Bypass without interrupting the output to the
connected equipment.
Disable
UPS Diagnostic
[Battery Test] [Alarm Test] [Indicator Test] [Fan Test]
[Battery Test]
[Activate?]
Starts a manual battery test, UPS will operate 10
seconds on Battery mode to check battery condition.
Starts a manual Alarm test, buzzer will sound for
5 seconds.
Starts a manual Indicator test, UPS will light all LED
and LCD background 5 seconds.
Starts a manual Fan test, UPS will operate fan with full
speed 5 seconds.
None
Audible Alarms
[Disable] [Enable] [Only Battery Low]
User can [Disable] or [Enable] the buzzer sound and
also can set [Only Battery Low] to have alarm only
when battery low on battery mode.
Enable
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
Sets the actual EBM (extended battery modules)
number to get the correct estimated runtime.
0
Wiring Fault
[Disable] [Enable]
Sets [Disable] or [Enable] the auto checking of Input
wiring fault.
Disable
NCL Control
[Outlet On] [Outlet Off]
Sets Non-Critical Load (NCL) [Outlet On] or [Outlet
Off] directly. When the user sets NCL [Outlet Off] ,
the NCL output power will turn off directly.
Outlet On