Plug Load Applications (WA100-PM)
ii. Appendix 1: Installation Advisory - Plug Load Applications (WA100-PM)
1
Plug load control functionality for the WA100-PM is made available with WA100-PM firmware provided in ControlScope
Manager version 3.5.3.1. During testing the Plug Load cycles on/off in sync with the lighting load. Relays used to control
plug loads must be compliant with UL498 (Attachment Plug and Receptacles) or equivalent.
Wiring for Combination Plug Load (Basic Aux Relay) and Dimming Light
In the wiring diagram below, the WA100-PM is used to control both a
dimming light and a plug load circuit.
Perform Installation Test Suite 1
Perform Installation Test Suite 1
Wiring for Combination Plug Load (Basic Aux Relay) and On/Off Light
In the wiring diagram below, the WA100-PM is used to control both an
On/Off light and a plug load circuit.
*0-10V Dimming output, 5 mA available, Up to 10 LED drivers or fluorescent
ballasts typical; the chance of noise on the signal increases with more.
**Relays used to control plug loads must be compliant with UL498
(Attachment Plug and Receptacles) or equivalant.
Line Voltage
Wires
WHITE Neutral
RED
Switched
Load
120-277VAC
BLACK Hot 120-277VAC
Hot
Neutral
RED 24VDC Power
Aux.
Relay
(20A)
+24VDC
GND
GREEN Digital Ouptut LSD
Neutral
Hot
Hot
Low Voltage
Wires
Cap unused
wires.
www.daintree.net
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
C
US
IEEE Address:
00228103007-00000
Load
Black
Hot
Neut
Red
White
Blue (Digital In 1)
Yellow (Digital In 2)
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
Relay
WA100-PM
15A
15A+45mA
45mA
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
CAN ICES-3 (B)/NMB-3(B)
RoHS
GRAY (-) Analog Ground
VIOLET (+) 0-10V Analog Output (dimming control)
*
Dimming Ballast
or LED Driver
(0-10VDC)
Plug Load
**
Line Voltage
Wires
WHITE Neutral
RED
Switched
Load
120-277VAC
BLACK Hot 120-277VAC
Hot
Neutral
RED 24VDC Power
Aux.
Relay
(20A)
+24VDC
GND
GREEN Digital Ouptut LSD
Neutral
Hot
Hot
Low Voltage
Wires
Cap unused
wires.
www.daintree.net
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
C
US
IEEE Address:
00228103007-00000
Load
Black
Hot
Neut
Red
White
Blue (Digital In 1)
Yellow (Digital In 2)
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
Relay
WA100-PM
15A
15A+45mA
45mA
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
CAN ICES-3 (B)/NMB-3(B)
RoHS
Ballast
or LED Driver
(non-dimming)
Plug Load
**
OFF
ON
DIP Switch Positions:
Driver: On/Off
Plug Load: On/Off
1 2 3 4 5 6
O
N
(# 2,4 ON)
DIP Switches
Wired
Sensor:
None
OFF
ON
DIP Switch Positions:
Driver: On/Off +
0-10V dimming
Plug Load: On/Off
1 2 3 4 5 6
O
N
(# 2,3 ON)
DIP Switches
Wired
Sensor:
None