Wireless Adapter (WA100-PM)

Joining the ZigBee Lighting Control Network 

After the Installation Test is complete the WA100-PM is ready to communicate with the Daintree Wireless Area Controller 
(WAC) and the Daintree ControlScope Manager (CSM) web-based lighting management user interface. Upon commissioning, 
the WA100-PM “Join” LED turns on solid and remains on as long as the WA100-PM is included in the ZigBee Network. 

After joining the network, the low voltage devices connected to the WA100-PM do not directly control the lights that are 
wired to the same WA100-PM. The control signals from the low voltage devices pass through the WA100-PM and are sent 
wirelessly to the ControlScope network. Depending on the zone and device configuration in the CSM, wireless signals from 
the WAC to the WA100-PM determine the operation of the light(s).

For more information about configuring the lighting control network, see the instructions and on-line help provided with the 
ControlScope Manager application.

Troubleshooting 

 

The Installation Test procedure fails.

1. Confirm that the WA100-PM is powered.
2. Check the connections from the WA100-PM to the driver(s) and low voltage control devices.
3. Check to be sure the WA100-PM DIP switch settings are correct.
4. Press and hold the Reset button for 3 seconds to reset the WA100-PM.
5. Perform the Installation Test again.

  

Connected lights do not turn Off during the occupancy sensor Installation Test.

1. Make sure the sensor is not detecting occupancy.
2. Check the occupancy sensor time delay and make sure it is set for minimum.

When the ControlScope lighting control network is commissioned, time delays are set in the Daintree

  CSM system. These CSM “Off delays” start counting down after the sensor’s internal time delay expires. 
  Therefore, set occupancy sensors for the minimum time delay during the WA100-PM installation.

  

The red Error LED is flashing once every second.

DIP switch configuration is invalid. At least one DIP switch must be On to enable an interface. 
1. Enable the interface(s) that are connected by turning appropriate DIP switch(es) On.
2. Press the blue 

Reset button for 3 seconds to reset the unit.

26

Summary of Contents for WA100-PM

Page 1: ...n to indicate its location 4 Mount the WA100 PM in the driver cavity of the light fixture or external to the light fixture or to a junction box approved for the application See Mounting page 13 5 Conn...

Page 2: ...xpected operation After you change DIP switch settings you need to press the blue Reset button for 3 seconds to reset the unit Release the button when the green Joined and red Error LEDs begin flashin...

Page 3: ...0 See Figure 12 No Driver sensors only provides wireless adaptation to connected occupancy sensor and or photosensor only No driver control Sensor To provide wireless adaptation for sensors set DIP sw...

Page 4: ...Line voltage wiring connects to the electrical supply circuit and to the driver s The Black Hot flying lead and the Red Switched Load flying lead are 14AWG The White Neutral flying lead is 18AWG Low v...

Page 5: ...7 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM 15A 15A 45mA...

Page 6: ...cent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1...

Page 7: ...ature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow...

Page 8: ...DC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blu...

Page 9: ...ltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Te...

Page 10: ...e chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24V...

Page 11: ...ent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1h...

Page 12: ...Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 0...

Page 13: ...t Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Red Blue Digital In 1 Yellow Digital In 2...

Page 14: ...Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents...

Page 15: ...A Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digi...

Page 16: ...s Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDO...

Page 17: ...75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue D...

Page 18: ...57 CAN ICES 3 B NMB 3 B RoHS WA100 PM REGULAR Line Voltage 120 277VAC LVS Model RRU X UM NC COM NO WHITE Neutral Hot NC COM NO RED BLACK BLUE RED BLUE YELLOW Connect 120VAC to BLK 277VAC to ORG FIXTUR...

Page 19: ...r LED Driver 0 10VDC WA100 PM Wireless Adapter WA100 PM Set DIP switches and perform Installation Test appropriate to 0 10v dimming and connected sensors In this application the WA100 PM is powered by...

Page 20: ...eep them neat out of the way and protected against shorting or interference with other components wiring or devices It is best to trim unused wires to about 5 inches in length isolate them using a wir...

Page 21: ...The WA100 PM can be secured at the other end using the integral screw tab Alternatively it can be mounted externally to a junction box enclosure or fixture housing through a 1 2 knockout Fig 19 Mounti...

Page 22: ...aves significant time during the commissioning process Record IEEE Addresses If you have not already done so be sure that each WA100 PM s IEEE address last 4 or 5 digits is recorded on the facility fl...

Page 23: ...and repeats 2 Check that the lights connected to the driver cycle from maximum to minimum brightness then turn Off then repeat 3 Press and immediately release the blue Reset button The red Error LED f...

Page 24: ...it testing 4 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when the green Joined LED and the red Error LEDs begin flashing Test Suite 6 Photos...

Page 25: ...sor the light turns On 6 Press and immediately release the Reset button to exit testing 7 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when t...

Page 26: ...e Manager application Troubleshooting The Installation Test procedure fails 1 Confirm that the WA100 PM is powered 2 Check the connections from the WA100 PM to the driver s and low voltage control dev...

Page 27: ...L x 1 7 W x 1 18 H 10 1 L x 1 7 W x 1 18 H with mounting bracket Driver references include ballasts unless otherwise noted FCC warning message This equipment has been tested and found to comply with t...

Page 28: ...t 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red Whit...

Page 29: ...o 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0...

Page 30: ...ss 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM...

Reviews: