Wireless Adapter (WA100-PM)
Installation Tests
All lighting devices, including wireless adapters, must be tested for proper operation.
After setting the DIP switches for your application, mounting, wiring low voltage, wiring line voltage, powering up and
resetting the unit, perform the recommended Installation Test. The Installation Test mode automatically times out after
5 minutes of no activity.
While the WA100-PM is in Installation Test mode, the low voltage devices connected to the WA100-PM directly control
the lights wired to the same WA100-PM. After you exit the Installation Test mode, the lights turn On and are NOT
controlled by the devices connected to the WA100-PM. After commissioning the ControlScope system, lighting control is
determined by configuration settings in the ControlScope Manager.
IMPORTANT NOTICES
Complete Installation Tests
Successful commissioning is dependent on testing each wireless-adapted lighting fixture and/or control device
at the time of installation. Finding installation issues or device problems earlier saves significant time during the
commissioning process.
Record IEEE Addresses
If you have not already done so, be sure that each WA100-PM’s IEEE address (last 4 or 5 digits) is recorded on the
facility floor plan. You can use the 4 or 5 digit label supplied with the WA100-PM or you can write the last 4 or 5
digits on the floor plan. This information will be used during the commissioning process.
After the lighting installation is complete, a marked-up copy of the facility floor plan showing the identity and
location of each wireless adapter (including associated light fixtures, switches and sensors) should be available. This
will simplify and expedite the commissioning process.
Test Suite 1:
On/Off, Dimming, Alternate Switching or Bi-Level Drivers Only
1. Press and immediately release the blue Reset button. The red Error LED flashes once, then pauses and repeats.
2. Check that the connected lights cycle On and Off, or cycle from maximum to minimum brightness then turn
Off per the DIP switch configuration.
3. Press and immediately release the Reset button to exit testing.
4. Press and hold the blue RESET button on the WA100-PM for 3 seconds to reset the unit. Release the button
when the green Joined LED and the red Error LEDs begin flashing.
22