Wireless Adapter (WA100-PM)

DIP Switch Mode descriptions

Light Adapter Mode

Control Type 
    

On/Off + 0-10V dimming: provides On/Off control using its line voltage Switched Load connection to the driver(s). 

              It also provides 0-10V dimming control to the driver(s).

    

On/Off (no dimming): provides On/Off control using its line voltage Switched Load connection, and its low voltage    

              digital output to an external relay. Note, both outputs are switched at the same time in this driver control mode. 

    Alternate: provides On/Off switching for one driver load using its line 
              voltage Switched Load connection, and its low voltage digital 
              output to an external relay to switch a second driver load. This allows 
              lighting level control for no load (0%), one or the other of the two loads, 
              and both loads (100%). See Figure 13.

    Bi-Level: provides On/Off switching for one driver with two loads using its
              line voltage Switched Load connection and low voltage digital output 
              an external relay to switch the second load. This allows lighting level 
              to control for no load (0%), partial load (according to driver capability) 
              or full load (100%). See Figure 12.

    No Driver (sensors only): provides wireless adaptation to connected occupancy sensor and/or photosensor only. 
        No driver control.

Sensor
      To provide wireless adaptation for sensors, set DIP switches 1, 5 & 6 according to the type(s) of sensors  

 

 

      connected to the WA100-PM. 

Range Extender
      The WA100-PM joins the ZigBee network and acts only as a wireless repeater to improve the wireless range   

 

      and/   or  reliability. No lights or devices are connected to the WA100-PM. 

Switch Adapter Mode

Switch Type
    

Dimming: operating the connected switch generates dimming and On/Off signals.   

    

On/Off (no dimming): operating the connected switch generates On/Off signals.  

    Alternate: operating the connected switch will switch separate drivers, providing no load (0%), partial 
              load (one or the other of the two loads, according to the driver loading) or full load (100%). 

  

    Bi-Level: operating the connected switch will switch loads independently in a bi-level driver (or 2 drivers), 
              providing no load (0%), partial load (according to the driver capability or driver loading) or full load (100%).

                 Bi-Level Switching States

Intensity Level  WA100 Switched  Aux Relay

Off (0%) 

Off 

Off

Medium (1-99%) 

On

 

Off

Maximum (100%) 

On 

On

                 Alternate Switching States

Intensity Level  WA100 Switched  Aux Relay

Off (0%) 

Off 

Off

Low (1-49%) 

On

 

Off

Medium (50-99%) 

Off

 

On

Maximum (100%) 

On 

On

3

Summary of Contents for WA100-PM

Page 1: ...n to indicate its location 4 Mount the WA100 PM in the driver cavity of the light fixture or external to the light fixture or to a junction box approved for the application See Mounting page 13 5 Conn...

Page 2: ...xpected operation After you change DIP switch settings you need to press the blue Reset button for 3 seconds to reset the unit Release the button when the green Joined and red Error LEDs begin flashin...

Page 3: ...0 See Figure 12 No Driver sensors only provides wireless adaptation to connected occupancy sensor and or photosensor only No driver control Sensor To provide wireless adaptation for sensors set DIP sw...

Page 4: ...Line voltage wiring connects to the electrical supply circuit and to the driver s The Black Hot flying lead and the Red Switched Load flying lead are 14AWG The White Neutral flying lead is 18AWG Low v...

Page 5: ...7 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM 15A 15A 45mA...

Page 6: ...cent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1...

Page 7: ...ature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow...

Page 8: ...DC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blu...

Page 9: ...ltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Te...

Page 10: ...e chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24V...

Page 11: ...ent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1h...

Page 12: ...Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 0...

Page 13: ...t Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Red Blue Digital In 1 Yellow Digital In 2...

Page 14: ...Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents...

Page 15: ...A Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digi...

Page 16: ...s Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDO...

Page 17: ...75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue D...

Page 18: ...57 CAN ICES 3 B NMB 3 B RoHS WA100 PM REGULAR Line Voltage 120 277VAC LVS Model RRU X UM NC COM NO WHITE Neutral Hot NC COM NO RED BLACK BLUE RED BLUE YELLOW Connect 120VAC to BLK 277VAC to ORG FIXTUR...

Page 19: ...r LED Driver 0 10VDC WA100 PM Wireless Adapter WA100 PM Set DIP switches and perform Installation Test appropriate to 0 10v dimming and connected sensors In this application the WA100 PM is powered by...

Page 20: ...eep them neat out of the way and protected against shorting or interference with other components wiring or devices It is best to trim unused wires to about 5 inches in length isolate them using a wir...

Page 21: ...The WA100 PM can be secured at the other end using the integral screw tab Alternatively it can be mounted externally to a junction box enclosure or fixture housing through a 1 2 knockout Fig 19 Mounti...

Page 22: ...aves significant time during the commissioning process Record IEEE Addresses If you have not already done so be sure that each WA100 PM s IEEE address last 4 or 5 digits is recorded on the facility fl...

Page 23: ...and repeats 2 Check that the lights connected to the driver cycle from maximum to minimum brightness then turn Off then repeat 3 Press and immediately release the blue Reset button The red Error LED f...

Page 24: ...it testing 4 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when the green Joined LED and the red Error LEDs begin flashing Test Suite 6 Photos...

Page 25: ...sor the light turns On 6 Press and immediately release the Reset button to exit testing 7 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when t...

Page 26: ...e Manager application Troubleshooting The Installation Test procedure fails 1 Confirm that the WA100 PM is powered 2 Check the connections from the WA100 PM to the driver s and low voltage control dev...

Page 27: ...L x 1 7 W x 1 18 H 10 1 L x 1 7 W x 1 18 H with mounting bracket Driver references include ballasts unless otherwise noted FCC warning message This equipment has been tested and found to comply with t...

Page 28: ...t 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red Whit...

Page 29: ...o 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0...

Page 30: ...ss 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM...