Plug Load Applications (WA100-PM)
2
Wiring for Combination Plug Load (Aux Relay with
Input Control Signal) and Dimming Light
In the wiring diagram below, the WA100-PM is used to
control both a dimming light and a plug load circuit.
Perform Installation Test Suite 1
Line Voltage
Wires
WHITE Neutral
RED
Switched
Load
120-277VAC
BLACK Hot 120-277VAC
Hot
Neutral
RED 24VDC Power
RED 24VDC
RED
RED
Control Output
BLACK Common
BLUE
GREEN
Ground
GREEN Digital Ouptut LSD
Neutral
SW Hot
Hot
Hot
Low Voltage
Wires
Cap unused
wires.
www.daintree.net
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
C
US
IEEE Address:
00228103007-00000
Load
Black
Hot
Neut
Red
White
Blue (Digital In 1)
Yellow (Digital In 2)
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
Relay
WA100-PM
15A
15A+45mA
45mA
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
CAN ICES-3 (B)/NMB-3(B)
RoHS
GRAY (-) Analog Ground
VIOLET (+) 0-10V Analog Output (dimming control)
*
Dimming Ballast
or LED Driver
(0-10VDC)
Aux Relay with input
control signal (20A)
Plug Load
**
OFF
ON
DIP Switch Positions:
Driver: On/Off +
0-10V dimming
Plug Load: On/Off
1 2 3 4 5 6
O
N
(# 2,3 ON)
DIP Switches
Wired
Sensor:
None
*0-10V Dimming output, 5 mA available, Up to
10 LED drivers or fluorescent ballasts typical; the
chance of noise on the signal increases with more.
**Relays used to control plug loads must be
compliant with UL498 (Attachment Plug and
Receptacles) or equivalant.