Part No. 4801-5338 Rev 2-2015
Evolution 4000
35 of 86
**TEMPERATURE RAMPING**
(1)Number of Points = 10 (2)Ramping = Off
(3)Preheat Target = 95.0° (4)Preheat = Off
(5)Target Temperature Differential
(6)POINT (7)DAY (8)TARGET
1
1
90.0°
2
5
88.0°
3
10
86.0°
4
15
84.0°
5
20
82.0°
6
25
80.0°
7
30
78.0°
8
35
76.0°
9
40
74.0°
10
45
72.0°
TARGET TEMPERATURE DIFFERENTIAL
(a)Enabled = Yes
(b)Target Adjust = +5.0°
(c)Adjust Between 11:00a and 1:00p
7.7
Growout Curve
The Growout Curve is used to adjust the temperatures and/or minimum vent requirements automatically by
the grow-out day. The specific Growout Curve screen features and setting options will depend on whether
the Optimum Mode feature is turned ON or OFF. The Optimum Mode feature is selected by entering
“Program Setup” and then “General Settings”. Refer to
Section 7.1
.
7.7.1 Growout Curve With Optimum Mode OFF
(1)
Number of Points –
Select 2
through 10 points.
(2)
Ramping –
Select On or Off to
enable or disable ramping.
(3)
Preheat Target –
Target
Temperature for preheating.
(4)
Preheat –
On or Off. Preheat
allows the controller to run the
target to a higher set target
temperature for preheating the
house.
(5)
Target Temperature Differential
– When enabled, this feature will adjust the target temperature
either higher or lower by the selected number of degrees during the selected time of day.
a.
Enabled
– Select Yes
to enable or No to
disable Target
Temperature
Differential.
b.
Target Adjust
– The
desired degrees above
or below the Target
Temperature.
c.
Adjust Between
– The
selected time of day for
which the Target
Temperature
Differential will occur.