Part No. 4801-5338 Rev 2-2015
Evolution 4000
42 of 86
** Cool Negative Properties **
These stages typically operate sidewall fans
Since they are not allowed to operate during
Tunnel Ventilation.
(1) Transitional Stage Override = Yes
(2) Override on Stage # 16
7.11 Stage Properties
The Stage Properties screen is where you link to set up specific parameters for the heating and cooling modes.
Stage Properties gives you a definition of how a stage will operate and allows you to add additional variables
to some of the properties.
(1)Heat Properties –
See Section 7.11.1
(2)Cool Stir Properties –
See Section 7.11.2
(3)Cool Negative Properties –
See Section
7.11.3
(4)Cool Negative Tunnel Properties –
See
Section 7.11.4
(5)Cool Tunnel Properties –
See Section
7.11.5
(6) Cool Evaporative Properties -
See
Section 7.11.6
(7) Natural Ventilation Properties
- See
Section 7.11.7
7.11.1 Heat Properties
There is one heat property to be setup. Set
to “Yes” if it is desired to operate the heat
stage only during minimum ventilation.
Otherwise the control will allow a heat
stage to operate at the same time a cool
stage is operating if they are looking at
different sensors.
7.11.2 Cool Stir Properties
This allows stir fans to act as mixing fans
during tunnel ventilation.
(1) Allow to operate in Tunnel
– Select
Yes or No.
YES
= The stir fans operate in any
ventilation mode.
NO
= The stir fans will NOT operate
during tunnel ventilation.
7.11.3 Cool Negative Properties
The following parameters can be set:
(1) Transitional Stage Override
– Yes or
No
(2) Override on Stage
– Set to an
available Stage Number.
This feature is used to turn
Cool Negative
Fans
off before entering tunnel ventilation.
Functionality: When the Override is set (Override on Stage # XX ) to a specific
Cool Negative Tunnel
Stage
, the Stage turns all of the
Cool Negative Fans
OFF when the Stage comes ON.
Example: Turning 36” Sidewall Fans OFF when a 48” Negative Tunnel Fan comes ON while still pulling air
through the vent boards.
** Stage Properties **
(1)Heat Properties
(2)Cool Stir Properties
(3)Cool Negative Properties
(4)Cool Negative Tunnel Properties
(5)Cool Tunnel Properties
(6)Cool Evaporative Properties
(7)Natural Ventilation Properties
** Cool Stir Properties **
These stages typically operate fans
That are used to stir the air inside
The building. They operate in all
Ventilation modes.
(1)Allow to operate in Tunnel = No
** Heat Properties **
Heat Stages operate heating devices
such as heaters or brooders. The
following are additional properties.
Operate during Minimum Vent only = No