EZT-430i Communications Manual
Operation
CSZ
EZT-430i
REVC
A.18
4025
(0x0FB8)
Wait For Analog 3, Ramp/Soak Steps
4026
(0x0FB9)
Wait For Analog 3, Value, Ramp/Soak Steps
4030
(0x0FBE)
Event Output 1, Ramp/Soak Steps
W
0
1
-
4031
(0x0FBF)
Event Output 2, Ramp/Soak Steps
W
0
1
-
4032
(0x0FC0)
Event Output 3, Ramp/Soak Steps
W
0
1
-
4033
(0x0FC1)
Event Output 4, Ramp/Soak Steps
W
0
1
-
4034
(0x0FC2)
Event Output 5, Ramp/Soak Steps
W
0
1
-
4035
(0x0FC3)
Event Output 6, Ramp/Soak Steps
W
0
1
-
4036
(0x0FC4)
Event Output 7, Ramp/Soak Steps
4037
(0x0FC5)
Event Output 8, Ramp/Soak Steps
4043
(0x0FCB)
Rate, Ramp Rate Step
4044
(0x0FCC)
Ramp Set Point Channel 1, Ramp Time Step
W
-32768
32767
*F2
4045
(0x0FCD)
Ramp Set Point Channel 2, Ramp Time Step
W
-32768
32767
*F2
4046
(0x0FCE)
Channel 1 PID Set, Ramp/Soak Steps
4047
(0x0FCF)
Channel 2 PID Set, Ramp/Soak Steps
4048
(0x0FD0)
Guaranteed Soak Channel 1, Ramp/Soak Steps
W
0
1
-
4049
(0x0FD1)
Guaranteed Soak Channel 2, Ramp/Soak Steps
W
0
1
-
4050
(0x0FD2)
Jump to Profile, Jump Step
4051
(0x0FD3)
Jump to Step, Jump Step
W
1
64
-
4052
(0x0FD4)
Jump Repeats, Jump Step
W
1
999
-
4060
(0x0CSZ)
End Action, End Step
4061
(0x0FDD)
End Idle Setpoint Channel 1, End Step
W
-32768
32767
*F2
4062
(0x0FDE)
End Idle Setpoint Channel 2, End Step
W
-32768
32767
*F2
Notes:
*D
R/W Specifies readable / writable data and W specifies a write only control value.
*E1
Parameter
Value
Description
1 Create
profile
2
Insert step
3
Delete current profile
4
Delete step
5 Start
profile
255
Delete all profiles
Note:
EZT-430i only supports the create profile and start profile
commands. When a value of 1 is written to the register, EZT-430i is
placed in profile receive mode in which all following write commands are
seen as profile data. Once the end step is detected, the profile receive
mode will end.
When a value of 5 is written to the register, EZT-430i will start the
currently loaded profile if it is not already running.
Any other non-supported command will be ignored.