EZT-430i Communications Manual
EZT-430i
Data
Registers
CSZ
EZT-430i
REVC 5.8
(standard serial interface)
The following 14 registers of the automatic program contain the data for step 1 of the program.
Register
Address
Parameter Description
Data
D
Range
*E
*F
Type Low
High Unit
114
(0x0072)
Step Number
*
W 0 63 -
115
(0x0073)
Step Type
W
*E5
*E5
-
116
(0x0074)
Ramp Target Setpoint Loop 1
W
-32768
32767
PV
117
(0x0075)
Ramp Time or Ramp Rate
W
0
5999
-
118
(0x0076)
Event Selections 1, 2, 3
W
*E6
*E6
-
119
(0x0077)
Holdback Type Loop 1
W
*E7
*E7
-
120
(0x0078)
Dwell Time
W
0
9999
-
121
(0x0079)
Jump Step
W
0
63
-
122
(0x007A)
Jump Cycles
W
1
9999
-
123
(0x007B)
Final Setpoint Loop 1
W
-32768
32767
PV
124
(0x007C)
Ramp Target Setpoint Loop 2
W
-32768
32767
PV
125
(0x007D)
Event Selections 4, 5, 6
W
*E8
*E8
-
126
(0x007E)
Holdback Type Loop 2
W
*E7
*E7
-
127
(0x007F)
Final Setpoint Loop 2
W
-32768
32767
PV
*
The
Step Number
must be offset by 1 when writing step data to EZT-430i . Steps 1-64 will be sent with the
step number as a value of 0-63 (-1 offset).
All remaining steps of the program follow the same format and data structure as is represented for
step one above. Up to the following 882 registers are used to contain the additional step data of the
program as required for steps 2 through 64. Since few if any programs will contain the maximum of
64 steps, it is only necessary to write the step data for the number steps used in the automatic
program.
128 (0x0080) – 141 (0x008D)
Program Step 2 Data Registers
142 (0x008E) – 155 (0x009B)
Program Step 3 Data Registers
156 (0x009C) – 169 (0x00A9)
Program Step 4 Data Registers
170 (0x00AA) – 183 (0x00B7)
Program Step 5 Data Registers
184 (0x00B8) – 197 (0x00C5)
Program Step 6 Data Registers
198 (0x00C6) – 211 (0x00D3)
Program Step 7 Data Registers
212 (0x00D4) – 225 (0x00E1)
Program Step 8 Data Registers
226 (0x00E2) – 239 (0x00EF)
Program Step 9 Data Registers
----------------------------------------------------------------------------------------------
through
----------------------------------------------------------------------------------------------
996 (0x03E4) – 1009 (0x03F1)
Program Step 99 Data Registers
Notes:
*D W Specifies write only data.