EZT-430i Communications Manual
EZT-430i
Data
Registers
CSZ
EZT-430i
REVC 5.6
(standard serial interface)
*B10
Parameter
Value
Description
Bit0
Automatic Program Run Mode
Bit1
Automatic Program Hold Mode
Bit2 Static
Mode
Bit3
Auto Tune Mode
Bit4 Manual
Mode
Bit5 Off
Mode
Bit6 Failure
Transfer
Bit7
Automatic Program Ramp Up
Bit8
Automatic Program Ramp Down
Bit9
Automatic Program Soak
Bit10
Alarm 1 Active
Bit11
Alarm 2 Active
Bit12
Alarm 3 Active
Bit13
Event 1 On
Bit14
Event 2 On
Bit15
Event 3 On
*B11
Parameter
Value
Description
0 No
Error
4
Illegal Setup Values
10
Comm Error – Bad Function Code
11
Comm Error – Register Out of Range
14
Comm Error – Write Read Only Data
15
Comm Error – Out of Range Data
25
Holdback Time Out
26
Auto Tune Error
27
Input Type Requires Calibration
29 EEPROM
Error
30
Cold Junction Failure
39 Sensor
Break
40
A to D Failure
Note:
The “alarm active” and “event on” status bits can not be used for
determining alarm or event status. The alarm and event activation is
based upon loop configuration. Do monitor alarm and event status, use
registers 5 and 12 respectively.