HV DTemp Measurement System – Mounting and Installation
User Guide
27
Version 01.00 // 2021
Fig. 4-11: Encoding switches, top side of controller
3. Encoding switches 1-4 for specifying the controller ID
4. Encoding switch "Termination" for terminating a controller
Switch position
Function
Left
Off
Right
On
Tab. 4-3: Encoding switch position
4 3 3 6 Setting the controller ID
Switch
ID
1
2
3
4
9
On
On
On
On
0
Off
On
On
On
1
On
Off
On
On
2
Off
Off
On
On
3
On
On
Off
On
4
Off
On
Off
On
5
On
Off
Off
On
6
Off
Off
Off
On
7
Tab. 4-4: Encoding switches, controller ID
4 3 3 7 Terminating a controller
The "Termination" switch (see Fig. 4-11) is used to terminate a controller. Switch position
"On" indicates that termination is enabled.
9 Only the switches "1" to "3" are required to set the controller ID. The ID switches "4" and "x" are without function.
➁
➀