HV DTemp Measurement System – Product Description
User Guide
13
Version 01.00 // 2021
➁
3 1 2 HV DTemp-M controller
HV DTemp-M controllers handle the addressing and power supply of the sensors. They
record the digital signals of the temperature sensors and transmit the temperature
values to the central unit (Fig. 3-2). One controller provides 16 digital inputs
for up to 16
(HV DTemp-M16) or 64 measuring points (HV DTemp-M64). The 4-pin sockets
➁
are used to
f
connect the controller to the central unit HV DTemp-P using a high-voltage-safe cable
or
f
daisy-chain the controller to a further controller using a connection cable.
It is possible to connect up to eight
2
HV DTemp-Mx controllers to one HV DTemp-P central
unit, depending on the license and thus the maximum number of measuring points.
Fig. 3-3: HV DTemp-M controller: top view
1. Sockets for sensors/sensor assemblies
2. Sockets for controllers/central unit
3. Status LED indicator (
→ chapter 3.2.3 "Status LED indicator (controller)"
)
4. Encoding switches (
→ chapter 4.3.3.5 "Encoding switches"
)
➁
➀
➀
➁
➃