cGas Detector for Indoor Public Spaces - Installation Manual
requirements of the system will be supplied by RPS-24VDC Remote Power
Supply de
vices. In an analog confi guration, a dedicated 4-20 mA signal wire is
connected to each transmitter and only the ground and power wires are daisy
chained.
If the cGas Detector is being connected to a BAS, DDC or other control panel
then either a 24 VDC power supply or 24 VAC Class 2 or better transformer
need to be used.
In all cases the voltage supply to the cGas Detector should never drop below 16
VDC or 12 VAC.
NOTE: WARRANTY VOID IF SOLID-CORE WIRE IS USED AT THE WIRING
TERMINAL STRIP.
When using solid core wiring for distribution (in the conduit), use stranded wire
pigtails 18 AWG within the enclosure to connect to the circuit board. The rigidity
of solid-core wire can pull a soldered terminal strip completely off a circuit
board and this will not be covered under warranty.