cGas Detector for Indoor Public Spaces - Installation Manual
Rev. A | 2020.11
Confirm?
>10.0 PPM NO2
N
>Y
Test Reading
10.0 PPM NO2
The test will start as soon as you press ENTER t
o confi rm and will remain in
the test mode as long as the Test Reading screen remains untouched, up to 5
minutes. To stop the test, press the UP or DOWN button. Test another reading
value or press ENTER to Exit.
7.6.3 Test Relay (models with Option -RLY installed)
NOTE:
Before testing the relay, notify the appropriate people so unnecessary
distress or response is not caused by activating fans or equipment or
inadvertantly calling the fi re department or other emergency response team.
From the main display, press ENTER.
Enter passcode 0001 using the UP button and ENTER button.
Enter Password
0001
Press ENTER to access the Test Menu.
Test Menu
Press Enter
In the Test Relay menu, the default entry is Untripped. Press ENTER and use the
UP button to change to Tripped. Press ENTER. You will hear a soft click and the
relay will activate accordingly, respecting its failsafe setting and ON/OFF delays.
Test Relay:SB
Untripped
Test Relay:SB
>Tripped
To stop the relay test, Press ENTER and the UP button to change to Untripped.
Press ENTER. You will hear a soft click and the relay will deactivate.
Test Relay:SB
>Untripped
When fi nished, press ENTER and then UP to Exit.