7.6.2 Test Digital Output
For digital models, for each gas channel, you can manually enter a gas reading
value of your choice (within the range of the sensor) that will be sent over the
digital network t
o test the connection and confi gured responses between the
cGas Detector and the DDC/BAS. You can do the same for relative humidity and
temperature if the -RHT option is installed.
From the main display, press ENTER.
Enter passcode 0001 using the UP button and ENTER button.
Enter Password
0001
Press ENTER to access the Test Menu.
Test Menu
Press Enter
In the Selected Channel menu, confi rm the correct channel is showing.
Selected Channel
CO
If you want to choose a different channel, press ENTER and use the UP button
to scroll to the next value. Press ENTER and continue.
Selected Channel
>NO2
The list to choose from will depend on included sensors and options:
• Gas Type (ie. CO)
• Gas Type (ie. CO2)
• Temperature
• Humidity
Press the UP button to fi nd Test Reading. To make a change, press ENTER and
then use the UP, DOWN and ENTER buttons to enter the value.
Test Reading
0 PPM NO2
Test Reading
>10.0 PPM NO2
Press ENTER and then again to Confi rm Y.