Control System
Crestron
Lighting
Switches
The CLW-SW wall box switch can also act as a Cresnet device reporting to a
Crestron control processor. The CLW-SW includes two isolated, non-polarized
Cresnet wires (plus a ground wire) for connecting to a Cresnet system over a twisted
pair wire with shield. In the absence of Cresnet communications, the switch can still
be used to control a load.
Refer to the CLW-SW, CLW-SWS, & CLS-SLVS Installation Guide (Doc. 6134)
for more installation information.
The CLW-SWS is similar to the CLW-SW with the added capability of working
with a slave unit (CLW-SLVS) in a multi-switch / single circuit application.
The CLW-SLVS is a slave unit that when used in conjunction with the CLW-SWS
acts as an additional switch control point in a multi-switch / single circuit
application. It does not connect to a Cresnet system and cannot be used without a
CLW-SWS. The CLW-SLVS does not have a mode selection switch and is not
programmable. It emulates the operation of the CLW-SWS to which it is connected.
The CLW-SW, CLW-SWS, and CLW-SLVS are available in white (designated by
part numbers ending in “W”), almond (designated by part numbers ending in “A”),
and black (designated by part numbers ending in “B”). These switches can be
covered with a decorative faceplate (not supplied).
CLW-SW, CLW-SWS, & CLS-SLVS Specifications
SPECIFICATION DETAILS
Power Requirements
Line Power (120 VAC, 60 Hz)
Switch Type
Single-Pole, Single-Throw
Load Type
Incandescent, Tungsten Halogen, Fluorescent,
Electronic Low Voltage, Magnetic Low Voltage,
General Purpose Fan
Load Ratings
Incandescent / Tungsten Halogen
1000 W (800 W)
Magnetic Low Voltage
1000 VA / 750 W (800 VA / 600 W)
Neon / Cold Cathode
1000 VA / 750 W (800 VA / 600 W)
Electronic Low Voltage
1000 W (800 W)
Fluorescent / HID
(High Intensity Discharge)
8 A (6.5 A)
General Purpose Fan
3.0 A (3.0 A)
Minimum Load
40W / 0.5A
Operating Temperature and Humidity
32°F to 104°F (0°C to 40°C)
10 to 90% Relative Humidity (Non-Condensing)
NOTE:
VA ratings are for input power to the transformer. If you do not know the
input power requirement of the transformer, use the bulb’s wattage rating to
determine proper rating.
NOTE:
Operating temperature affects load ratings. Refer to the Load Rating
specification in the table above for specific operating temperatures. Ratings are given
for 32°F to 86°F (0°C to 30°C) and 32°F to 104°F (0°C to 40°C) operation. Ratings
for 32°F to 104°F (0°C to 40°C) are in parentheses.
20
•
Lighting Control System Design
Design Guide – DOC. 5999A
Summary of Contents for Lighting Control System