cap screws surrounding the motion
controller.
Gently pull the faceplate forward to view
the back side of the circuit board behind
the faceplate.
Check that all terminal blocks are securely
mated onto the circuit board.
Motor runs roughly or makes strange noises
when jogging manually.
Run the auto‐tuning procedure outlined on page
Error! Bookmark not defined.
.
Both the FWD LIMIT and REV LIMIT fault
messages are displayed on the status screen and
the motor won’t move.
Make sure the Encoder/Limits cable is
plugged into the rear of the Stagehand.
Check the placement of your limit
switches, if both are physically activated,
adjust the placement to clear one or both
switches.
Check the limit switch wiring, confirm that
the switches are wired Normally Closed
(N.C.)
I’m trying to jog the motor, but the status display
shows “SET IP”.
The motion controller is in IP Address setting
mode, which happens when the knob is pressed
(either intentionally or just bumped in passing).
Turn the knob until the cursor is blinking over the
word CANCEL and then press the knob. The
motion controller will now be in normal mode and
can jog the motor again.
Technical
Support
Despite our best efforts and intentions to provide reliable equipment and clear instructions, there may come a
time that you need more direct, personal help. We are happy to do that too. Please get in touch in whatever
way is most convenient:
Phone: 401‐289‐2942. We’re open weekdays 8:30am – 5:00pm EST. If you call outside of normal
business hours (like during tech, or pre‐show check, or intermission), one of us will be on‐call with a cell‐
phone gaff‐taped to his hand. Listen to the message on our main phone number to get the cell phone
number of the technician on‐call.
Fax: 401‐289‐0259. Honestly, I don’t think anyone uses the fax for tech support, but you are free to be
the first.