Crane PROSSER STANDARD-LINE 9-81000 Series Installation And Operation Manual Download Page 11

11

valves or the units are spaced. 

CAUTION ! - When check valves are not used 

and a series system is accidentally shut down 

instantaneously (power failure), sufficient time 

must be allowed for pump impellers to stop 

rotating backwards before restarting.

NOTE:

 Pressure inside 3” discharge pumps or smaller should 

not exceed 100 PSI (231 ft of Head). Pressure inside 4” 

discharge pumps or larger should not exceed 200 PSI (462 

ft. of Head).

D-3.1) Report:

Included at the end of this manual are two start-up report 

sheets, these sheets are to be completed as applicable. Return 

one copy to the Prosser Pumps Service Department and store 

the second in the control panel or with the pump manual if no 

control panel is used. It is important to record this data at initial 

start-up since it will be useful to refer to should servicing the 

pump be required in the future.

D-3.2) Identification Plate:

Record  the  numbers  from  the  pump’s  identification  plate  on 

both START-UP REPORTS provided at the end of the manual 

for future reference.

D-3.3) Insulation Test:

Before the pump is put into service, an insulation (megger) 

test should be performed on the motor. The resistance values 

(ohms) as well as the voltage (volts) and current (amps) should 

be recorded on the start-up report.

SECTION E:  PREVENTIVE MAINTENANCE:

Prosser pumps are CSA approved. The following procedure 

must be followed to assure proper pump operation and unit 

CSA approval integrity.

1.) 

General Safety:

 Frequent inspection shall be made. All 

electrical parts, including the portable cable and wiring, shall 

be kept in a safe condition. 

KEEP CABLE GLAND NUTS 

TIGHT, CHECK FREQUENTLY.

 There shall be no openings 

into the casing of the electrical parts. The machine frame shall 

be effectively grounded. The power wires shall not be used 

for grounding. The operating voltage shall match the voltage 

rating of the motor(s).

2.) 

Servicing:

 Pump and control enclosures shall be restored 

to the state of original safety with respect to all lead entrances, 

etc., following disassembly.

3.) 

Renewals and Repairs:

 Special care shall be taken in 

making renewals or repairs. Leave no parts off. Use replacement 

parts furnished by the manufacturer. When any lead entrance 

is disturbed, the original leads or exact duplicates thereof shall 

be used.

4.) 

Fastenings:

 All bolts, nuts, screws and other means of 

fastenings and also threaded covers, shall be in place, properly 

tightened and secured.

5.) 

Cable Requirements:

 A heavy usage, type SOW 

submersible cable shall be used. Special care shall be taken 

in handling the cable against mechanical injury and wear. 

Connections and wiring to the power source shall be in 

accordance with all local electrical and safety codes.

6.) 

Shaft Seals:

 The seals should be inspected every 

1500 operating hours for wear (more often if abrasives are 

present). To make a quick check of the seal’s condition, drain 

and inspect the oil in the seal chamber (See Section F-1). 

If oil removed from the pump contains water or abrasives, 

replace seals.

7.) 

Amperage:

 Amperage should be checked periodically 

(at least weekly) to be certain that it does not exceed limits 

recommended by manufacturer on pump nameplate.

8.) 

Volts:

 If a generator is the power source, check daily for 

variation of voltage and cycles.

This pump is equipped with prelubricated bearings.

When a job is completed and before pumps are stored, 

drain the oil from the seal chamber (a must before freezing 

weather). If dirt or water are found in the oil, replace seals, 

bearings, lower “O” rings and oil.

SECTION F: SERVICE AND REPAIR

NOTE:

 All item numbers in ( ) refer to Figures 14 & 15 for 

10-15HP and 16 & 17 for 25-50HP.

WARNING ! - Electrical power to the pump motors 

must be disconnected and locked out to prevent 

any dangerous electrical hazards or personnel 

danger before any service work is done to the 

pump.

F-1) Electrical Inspection:

When pumps are returned from a field operation, or when 

a pump needs repair, prior to disassembly, and after 

disconnecting the unit from the power source, make electrical 

inspection of the pump, cable and control box. The test can 

be done by using a megger and an ohmmeter.

F-1.1) Insulation Resistance - Cable & Control:

Use the megger to measure the insulation resistance. Attach 

the megger probes to the pump lead side of the circuit breaker 

in the control box, one probe to the ground lead and one 

probe to a pump power lead.  Acceptable values of insulation 

resistance are 10 megohms or greater. If insulation resistance 

is below 10 megohms, the motor leads should be disconnected 

from the cable assembly so that the cable and motor can be 

tested separately.

Should the cable show insulation resistance of less than 10 

megohms, disconnect from control box and attach megger 

probes to the individual leads within the cable. Values below 

10 megohms of insulation resistance would indicate damage 

or moisture and cable should be replaced. Low values of 

insulation resistance below 10 megohms for the circuitry within 

the control box would indicate damage or moisture, Any bad 

parts should be replaced.

F-1.2) Insulation Resistance - Motor:

The insulation resistance of the motor stator can be measured 

by attaching one probe of the megger to the motor power 

leads and the other probe to the motor ground lead or to bare 

metal of the pump frame. Insulation resistance values under 

10 megohms would indicate presence of excessive moisture 

within the stator winding. Such moisture can be removed from 

the stator by placing the stator and frame assembly in an oven 

and baking the assembly at 250°- 275°F for two to three hours. 

Following such baking, re measure the insulation resistance 

to verify that a minimum of 10 megohms has been attained, if 

Summary of Contents for PROSSER STANDARD-LINE 9-81000 Series

Page 1: ...uct improvement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 096928 Rev Y Series 9 81000 9 81500 9 82500 9 85000 10HP thru 50HP 3450R...

Page 2: ... 85000 SERIES 25 26 NEMA 3R RainProof CONTROL CROSS SECTION PARTS LIST 27 NEMA 4 WaterTight CONTROL CROSS SECTION PARTS LIST 28 CONTROL SCHEMATIC Fig 20 29 GALVANIC PROTECTION KIT 29 SERIES ADAPTER KITS 30 RETURNED GOODS POLICY 31 WARRANTY 32 START UP REPORT 33 34 WARRANTY REGISTRATION SPECIAL TOOLS AND EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL TOOL KIT see parts list PRESSURE GAUG...

Page 3: ...ert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed manufacturers ...

Page 4: ... Phase Torque Curve Squirrel Cage Induction Insulation Class F CONTROL Three Phase Rainproof NEMA 3R NEMA 4 for 9 85000 Provides Circuit Breaker for overload and short circuit protection OPTIONAL EQUIPMENT Watertight NEMA 4 Control Series Adapter Kit Carrying Handle Viton Seals Hardened 440C Stainless Steel Impeller WARRANTY INVALID IF CORRECT PROSSER CONTROL IS NOT USED AT ALL TIMES PUMP SERIES W...

Page 5: ...5 inches mm MODEL A B 9 81000 27 38 696 24 00 610 9 81500 29 12 740 25 75 654 A B ...

Page 6: ...6 inches mm MODEL A B 9 82500 33 95 862 30 69 780 9 85000 36 68 932 33 69 856 A B ...

Page 7: ...ters For the location of the nearest Prosser Service Center check your Prosser representative or Crane Pumps Systems Inc Service Department in Piqua Ohio telephone 937 778 8947 or Crane Pumps Systems Canada Bramton Ontario 905 457 6223 SECTION C INSTALLATION C 1 Location These pumping units are self contained and are recommended for well type predewatering of building sites or pipelines sumping an...

Page 8: ...UMP B If the system is flowing more than the smaller pump can handle i e greater than Q the smaller pump Pump B will actually retard the flow and can induce cavitation in Pump A To predict the performance simply add the heads produced at a particular flow rate H M T H M A H M B See Fig 4 C 3 Liquid Level Controls If Applicable Attach ON float to discharge hose or pump cable at desired pump ON leve...

Page 9: ...ol This is critical or damage may occur Control enclosure must be operated with cover closed SECTION D START UP OPERATION D 1 Check Voltage and Phase Before operating pump compare the voltage and phase information stamped on the pump s identification plate to the available power Install proper safety ground connection to the green conductor to insure the motor pump and control remains at ground po...

Page 10: ...0 3450 K 30 0 208 0 6 4 SOW 1 100 0 30 0 30 0 30 9 81034 24 10 460 3 60 3450 K 15 0 104 0 12 4 SOW 0 650 1 14 1 14 1 14 9 81035 24 10 575 3 60 3450 K 12 0 83 0 12 4 SOW 0 650 2 00 2 00 2 00 9 81532 24 15 230 3 60 3450 J 39 5 288 0 6 4 SOW 1 100 0 21 0 21 0 21 9 81534 24 15 460 3 60 3450 J 19 7 144 0 12 4 SOW 0 650 0 75 0 75 0 75 9 81535 24 15 575 3 60 3450 J 15 6 110 0 12 4 SOW 0 650 1 21 1 21 1 2...

Page 11: ...1500 operating hours for wear more often if abrasives are present To make a quick check of the seal s condition drain and inspect the oil in the seal chamber See Section F 1 If oil removed from the pump contains water or abrasives replace seals 7 Amperage Amperage should be checked periodically at least weekly to be certain that it does not exceed limits recommended by manufacturer on pump namepla...

Page 12: ...es the pressure is still holding constant and no leaks are observed slowly bleed the pressure and remove the gauge assembly Replace the pipe plug 42 using a sealant If the pressure does not hold then the leak must be located and repaired CAUTION Always wear eye protection when working on pumps CAUTION Pressure builds up extremely fast increase pressure by TAPPING air nozzle Too much pressure will ...

Page 13: ...er or prying out with flat screw driver To remove inner shaft seal 10 remove snap ring 11 spring retainer 10a and spring 10b from shaft The diffuser 9 and the rest of the inner seal 10 can now be removed by tapping the diffuser with a plastic hammer until free Pull the lower end assembly from the stator frame assembly and check the rotor and stator for evidence of water oil electrical or mechanica...

Page 14: ...14 FIGURE 9 ...

Page 15: ...embly While disassembling check for indications of water leaks Remove cap screws 28 and washers 30 cable gland assembly 2 and o rings 25 from discharge head 22 Use care to avoid damaging the metal surface Remove cap screws 60 and washers 61 from cable clamp 2f Disconnect cable wires from stator leads by removing connectors 29 being sure that the stator s wires are identified before disconnecting C...

Page 16: ... outer case 21 over the frame 5 Press bearing 7 onto discharge end of rotor shaft and press bearing 46 with bearing retainer 57 onto suction end of rotor shaft It is IMPORTANT that this bearing be installed as shown in Figure 12 The outer race of bearing 46 that is imprinted with the words SUPPORT HERE must be positioned toward the diffuser 9 Axial thrust after start up is in the direction towards...

Page 17: ...ists of a six digit number which is specific to each pump and may be preceded by a alpha character which indicates the plant location This number will also be suffixed with a three or four digit number which indicates the date the unit was built Date Code EXAMPLE A012345 495 Reference the six digit portion Serial Number of the number when referring to the product G 2 MODEL NUMBER This designation ...

Page 18: ...Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Check rotation If power supply is three phase reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixtures as required to eliminate leakage 12 Check pump temperatu...

Page 19: ...19 FIGURE 14 PUMP SERIES 9 81000 9 81500 ...

Page 20: ...20 FIGURE 15 PUMP SERIES 9 81000 9 81500 ...

Page 21: ...HP HV 4 1 9 810105 Suction Case 10HP HH 1 9 815100 Suction Case 10 15HP HV 1 9 815105 Suction Case 15HP HH 5 1 9 610500 1 Frame 10HP 1 9 615500 2 Frame 15HP 6 1 9 610400 Rotor 10HP 230V 1 9 810630 Stator 10HP 230V 1 9 610400 Rotor 10HP 460V 1 9 810630 Stator 10HP 460V 1 9 610400 Rotor 10HP 575V 1 9 810635 Stator 10HP 575V 1 9 615400 Rotor 15HP 230V 1 9 815630 Stator 15HP 230V 1 9 615400 Rotor 15HP...

Page 22: ...ag Lead Ground 37 6 2 25001 4 Drive Screw 38 25oz 029034 Oil Cooling 39 1 2 21001 22 Lockwasher 1 4 Cad 40 4 2 23011 2 Hex Hd Screw 5 16 18 x 50 Lg Zp 42 1 2 32004 20 Pipe Plug 50 NPT Stainless 43 1 2 31003 122 O Ring 46 1 2 34004 Bearing Angular Ball 47 1 9 840752 Stator Dam 230 460V 1 9 840752 1 Stator Dam 575V 48 1 9 815350 Shaft Seal Outboard Silicon Silicon Viton 57 1 9 815311 Bearing Retaine...

Page 23: ...23 FIGURE 16 PUMP SERIES 9 82500 9 85000 ...

Page 24: ...24 FIGURE 17 PUMP SERIES 9 82500 9 85000 ...

Page 25: ...0100 8 Suction Case 50HP HV 5 1 9 840500 Frame 25HP 1 9 850500 Frame 50HP 6 1 137853 Rotor Stator 25HP 230 460V 1 137854 Rotor Stator 25HP 575V 1 137855 Rotor Stator 50HP 460V 1 137856 Rotor Stator 50HP 575V 7 1 2 34013 Bearing 8 1 2 30002 5 Bearing Loading Spring 9 1 9 840300 Diffuser 10 1 09917 Shaft Seal Inboard Carbon Ceramic Buna N 11 1 2 27002 125 Snap Ring 12 1 9 840310 Seal Retainer 13 1 2...

Page 26: ...2 21001 22 Lockwasher 1 4 Cad 40 4 2 23011 2 Hex Hd Screw 5 16 18 x 50 Lg Zp 42 1 2 32004 20 Pipe Plug 50 NPT Stainless 43 1 2 31003 122 O Ring 25HP ONLY 46 1 2 34016 Bearing Angular Ball 47 1 9 840750 Stator Dam 25HP 230 460V 1 9 840750 1 Stator Dam 25HP 575V 50H 460V 48 1 9 840350 Shaft Seal Outboard 25HP Silicon Silicon Viton 1 9 850350 Shaft Seal Outboard 50HP Silicon Silicon Viton 49 25 2 210...

Page 27: ...ame Plate 106 1 085809 Lable CSA 120 1 2 33016 Caution Label 121 1 9 810850 032 Circuit Breaker 10HP 230V 240V 34A 1 9 815850 136 Circuit Breaker 10HP 460V 600V 18A 1 9 810850 036 Circuit Breaker 10HP 575V 600V 13 6A 1 9 840850 036 Circuit Breaker 15HP 230V 600V 45A 1 9 815850 034 Circuit Breaker 15HP 460V 480V 22A 1 9 815850 136 Circuit Breaker 15HP 575V 600V 18A 1 9 825850 032 Circuit Breaker 25...

Page 28: ...34 Circuit Breaker 15HP 460V 480V 22A 1 9 815850 136 Circuit Breaker 15HP 575V 600V 18A 1 9 825850 032 Circuit Breaker 25HP 230V 240V 80A 1 9 825850 034 Circuit Breaker 25HP 460V 480V 40A 1 9 825850 036 Circuit Breaker 25HP 575V 600V 30A 1 9 850850 034 Circuit Breaker 50HP 460V 480V 60A 1 9 840850 134 Circuit Breaker 50HP 575V 600V 38A 122 1 2 33065 Wiring Diagram 3 Phase 123 2 2 12055 4 Connector...

Page 29: ...mately half full of electrical bounding grease part number 2 45003 1 4 Install washers and capscrews though zinc anode and into the frame holes partially filled with bonding grease and tighten securely 5 Route wire from anode to the suction nozzle Loosen suction nozzle capscrew washer and install wire between washer suction nozzle retighten capscrew Route other wire to discharge head and install u...

Page 30: ...O DESCRIPTION 1 2 32015 3 Nipple Reducer 4 NPT x 6 Lg 1 2 32046 1 Coupling Red Victaulic 5 x 4 4 1 51 6 Hex Hd Screw 3 8 16 x 5 50 Lg Zp 4 2 23013 84 Hex Hd Screw 3 8 16 x 5 00 Lg Zp P N 9 840770 QTY PART NO DESCRIPTION 1 2 32015 4 Nipple Victaulic 6 NPT x 6 Lg 1 2 32045 3 Coupling 6 Victaulic 5 2 23013 86 Hex Hd Screw 1 2 13 x 5 00 Lg Zp ...

Page 31: ... A RETURNED GOODS AUTHORIZATION CONTACT YOUR LOCAL CRANE PUMPS SYSTEMS INC DISTRIBUTOR Products Returned Must Be Cleaned Sanitized Or Decontaminated As Necessary Prior To Shipment To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty If...

Reviews: