APP Interface
52 / 79
Grid Frequency
60.00~72.00Hz
Settable
Power
Present
0
0.0%~100.0%
Settable
GridF.Max1
Figure 6-15 Curve of over frequency derating
In addition, the table listed below can provide detailed parameter information for you.
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
Unit
Over-Voltage Derate
VwCurveV1
Grid Volt of VwCurve
point V1
{100.00%, 110%}
106.00%
106.00%
106.00%
%
VwCurveP1
Power of VwCurve
point P1
{0%,110%}
100%
100%
100%
%
VwCurveV2
Grid Volt of VwCurve
point V2
{100%,115%}
110.00%
110.00%
110.00%
%
VwCurveP2
Power of VwCurve
point P2
{0%,110%}
0.0%
0.0%
0.0%
%
OpenLoopRespT
Open loop response
time
{0.5, 90.0}
10.0
10.0
10.0
Secs
OvrVoltDerEn
Over voltage
derating enable
{ Disable,
Enable}
Enable
Enable
Disable
Over-Frequency Derate
OvrFrqMin
The trigger
frequency of over
frequency derating
{60, 72}
60.04
60.04
60.50
Hz
OvrFrqMax
The end frequency
of over frequency
derating
{60, 72}
62.53
62.03
61.40
Hz
OvrFrqSlop
The rate of over
frequency derating
{0.01, 100}
30%
30%
0.16%
%
RecoveryFrq
The recovery
frequency of over
frequency derating
{58.8, 66}
59.96
59.96
60.00
Hz
OvrFrqRecoveryT
The recovery time of
over frequency
derating
{0,1200}
60
60
60
Secs
OvrFrqDerating
Mode
Over frequency
derating mode
{Disable, Enable}
Enable
Enable
Disable