APP Interface
58 / 79
Manual Turn ON/OFF
: Manual Power ON/OFF is required after Grid Code
setting or manual (fault) shut-down. Touch to submenu
“
Turn ON/OFF”.
Then move the cursor to “Turn ON” to start the inverter, the inverter will
start up and operate normally if the start-up condition is met. Otherwise,
the inverter will go to stand-by mode.
Normally, it is not necessary to Turn OFF the inverter, but it can be shut
down manually if Grid Code setting or maintenance is required.
Move the cursor to submenu “Turn ON/OFF”. Move the cursor to “Turn
OFF” and ensure, then the inverter will be shut down.
Automatic Turn ON/OFF
: The inverter will start up automatically when the
output voltage and power of PV arrays meet the set value, AC power grid
is normal, and the ambient temperature is within allowable operating range.
The inverter will be shut down automatically when the output voltage and
power of PV modules are lower than the set value, or AC power grid fails;
or the ambient temperature exceeds the normal range.