Troubleshooting
59 / 79
7
Troubleshooting
LED Indicator Troubleshooting
LED display of the inverter is shown as follows:
Figure 7-1 LED display of the inverter
Indicators and their indications are shown in Table 7-1.
LED
light
Name
Status Indication
POWER
Working
power light
ON
PV Energized (control panel starts to
work)
Flash
PV no power and AC Power on
OFF
No Power working
RUN
Grid-tied
operation
indication light
ON
In grid-tied power generation state
Flash
Derated running status (light up 0.5s,
light off 1.5s)
OFF
In other operation status or power
supply not working
GRID
Grid
status
indication light
ON
Grid is normal
Flash
Grid fault (light up 0.5s, light off 1.5s)
OFF
Power supply not working
FAULT
Fault
status
indication light
ON
Indicates a Fault
Slow
flash
Indicates Alarm (light up 0.5s, light off
2s)
Fast
flash
Protective action (light up 0.5s, light
off 0.5s)
OFF
No fault or power supply not working
ALL
Upgrade
status
flash
LCD or DSP upgrading
Table 7-1 LED Indicators and their indications
If the LED light indicates any faults, please perform troubleshooting according to