Technical Data
70 / 79
Max.
output
overcurrent
protection
300A
System parameters
Topology
Transformerless
Maximum efficiency
99.0%
China efficiency
98.5%
Standby/Night loss
<5W
Environmental parameters
Protection level
NEMA TYPE 4X
Cooling method
Variable speed cooling fans
Operating temperature
(3)
-22°F to +140°F / -30°C to +60°C (derating
from +107°F / +42°C)
Operating humidity
0-100%, No condensation
Operating altitude
(4)
2500m
,
No derating
Display and communication
Display
LED indicators, WiFi + APP
Communication
Modbus RS485/Ethernet TCP/IP/PLC/CAN
Structural parameters
Dimensions (WxHxD) (mm)
1050x690x400
Weight (kg)
119
Fused String Inputs
(5)
20A fuses provided (Fuse values up to 30A
acceptable)
Safety
Safety and EMC standards
UL1741_2018; CSA-22.2 NO.107.1-16; FCC
CFR 47 part15.
Grid-connected specification
IEEE1547_2003;
IEEE1547_2014;
IEEE1547_2018; CA Rule21; HECO Rule
14H; HECO-ML; ISO-NE.
Table 9-1 Datasheet of the inverter
Notes:
1.
When the DC input voltage is lower than 900V or higher than 1300V,
the inverter begins derating. Once the input voltage is between 900-
1300V, the inverter supports full output power. Derating curve of PV
input voltage are as shown in Figure 9-1.